SELF-DIAGNOSTIC ALARM CODES
Alarm Display Problem Cause Correc ve Ac on
Frost preven on
sensor and Abnor-
mal
temperature sensor
value
Indoor heat exchanger
temperature too low
TH3 temperature sensor
has a loose or broken
connec on
Do not use the air
condi oner if ambient
temperature is lower than
18°C (64°F)
Contact a quali ed service
agent
Refrigerant high
pressure switch
• Blocked air lter
Ambient temperature is
too high
Leak/cut o supply
water
• Clean air lter
Do not use the air
condi oner if ambient
temperature is higher
than 50°C (122°F)
Check water ow
Abnormal tempera-
ture sensor value
TH1(Outlet) temperature
sensor has a loose or
broken connec on
Contact a quali ed service
agent
Abnormal tempera-
ture sensor value
TH2(Inlet) temperature
sensor has a loose or
broken connec on
Contact a quali ed service
agent
Compressor over-
loaded
Ambient temperature is
too high
Unstable voltage
supply
Defec ve compressor
Over current relay
defect or broken
connec on
Do not use the air
condi oner if ambient
temperature is higher
than 50°C (122°F)
Contact a quali ed service
agent
• Replace compressor
Condensate water
level alarm
Condensate tank is full
Empty the water tank
A er installa on of the
water tank, press the
SPOT/COOL or ROOM/
COOL bu on to resume
opera on
Drain pump alarm
Drain pump defec ve or
improper hose connec-
on (including kink or
blockage)
Check the hose connec-
on and hose
• Replace drain pump
Table 1- Alarm Codes