POWERPATH™
NAC POWER SUPPLIES
Description
POWERPATH™ Series PS-12/24-8CP and PS-12/24-8MP are
power limited 8 amp power supply/chargers used to expand
the supervised power capability of a fire alarm control panel
(FACP) for notification appliance circuits (NAC).
The PS-12/24-8CP provides up to 200 milliamps of continuous
auxiliary output that can be used for control functions during
alarm (or up to 60 milliamps for 60 hour battery requirements).
The PS-12/24-8MP provides up to 3.5 amps of auxiliary output
that is available only during nonalarm condition for such
applications as door holder systems.
Both models provide regulated and filtered 12 or 24 VDC output
to four (4) Class “B” or two (2) Class “A” circuits. Each Class “B”
circuit has a rating of three (3) amps with a total output of up to
eight (8) amps. Each Class “A” circuit is rated at three (3) amps.
Two (2) Class “A” or Class “B” inputs from an FACP and two (2)
dry contact inputs are provided to trigger the outputs. The units
accept either 12 or 24 VDC inputs and provide 12 or 24 VDC
outputs. Both units support a full 8 amps of notification power
even if the battery is in a degraded mode and only AC power is
connected.
POWERPATH™ Series PS-12/24-8CP and PS-12/24-8MP are
compatible with all Wheelock 12 or 24 VDC Life Safety Notification
Appliances and with their Patented BUILT-IN SYNCHRONIZED
MODE feature, they can control and operate all of Wheelock’s
Synchronized Notification Appliances, including silencing
audibles while maintaining strobe activation.
Series PS-12/24-8CP
Series PS-12/24-8MP
(Batteries Not Included)
Features
Approvals
• Approvals Include: UL Standard 864, California State Fire
Marshal (CSFM), (New York City (MEA), Factory Mutual
(FM), Chicago (BFP) See Approvals by model in
Specification and Ordering Information
• Compliant with NFPA 72
Inputs
• Compatible with 12 or 24 VDC FACP
• 115 VAC @ 50/60 Hz or 240 VAC @ 50/60 Hz
• Two 12 or 24VDC NAC Initiating Circuits from host panel
• Two “Dry” contact input circuits
• Accepts 2 Class “A” or 2 Class “B” NAC circuit inputs
• Additional activation options are: NC contacts or open
collector of a transistor
Outputs
• 8 amperes rated supply current @ 12 or 24 VDC
• Filtered and regulated power supply outputs
• Class 2 rated power limited outputs
• Dip switch selectable options
• Field selectable 12 or 24 VDC outputs
• 4 Class “B” or 2 Class “A” or 1 Class “A” and 2 Class
“B” Notification Appliance Circuits)
• Each Class “B” output has a maximum rating of three
(3) amperes
• Each Class “A” output has a maximum rating of
three (3) amperes
• Code 3 (Temporal) option
• Steady output option
Copyright 2004 Wheelock, Inc. All rights reserved.
Outputs Cont.
• Built-In Wheelock Synchronization Protocol
• Input and output synchronization (including pass
through)
Supervision
• FACP NAC supervision steered to either input #1 or #2
• Common input and output trouble circuit
• Input and output LED indicators
• AC fail supervision (Form “C” contacts rated @ 1 amp
@ 24 VDC or 115 VAC)
• Battery presence and low battery supervision (Form
“C” contacts rated @ 1 amp @ 24 VDC or 115 VAC)
• Ground fault detection
• 4 latching LED’s for NAC trouble annunciation
Power
• Not Battery Dependent - Full 8A even if battery is
degraded
• Automatic switch over to standby batteries when AC
fails
• Supports sealed lead acid or gel type batteries
• Fused battery protection
• Thermal and short circuit protection with auto reset
• Supports both 7AH or 12AH batteries in the same
cabinet (Cabinet Size: 16" H x 12.25" W x 5" D)
Auxiliary Power
• Up to 200 mA continuous with PS-12/24-8CP
• Up to 3.5 amps nonalarm with PS-12/24-8MP
ACTION MESSAGES
COMMUNICATIONS
SYSTEMS