EasyManua.ls Logo

Whirlpool WASHER - Troubleshooting; Noisy Washer; Leaking Washer; Washer Stops, Wont Fill, Rinse or Agitate

Whirlpool WASHER
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PAGE 6
FOR SERVICE TECHNICIAN’S USE ONLY
DO NOT REMOVE OR DESTROY
Component Activation Chart
Output On/Off Details
UI Component Test N/AUpon activation, all LEDs are turned on. Pressing each button turns off
its LED. Rotating the cycle selector knob turns off each LED. Pressing
the ATM buttons changes their on-screen representations from black
to green.
Motor YES Status (On/Off) NOTE: Door must be closed.
If the motor does not turn on, go to TEST #3, page 12.
Heater1 (Electric)/ Heat On (Gas) YES Status (On/Off) NOTE: Door must be closed.
Attributes: Exhaust & Inlet Thermistor Reading.
When you turn on heat, the motor is turned on as well. If temp is
too high, system will automatically turn off heat.
• If the motor does not turn on, go to TEST #3, page 12.
• If no heat is detected, go to TEST #4, page 13.
Heater2 (Electric Only) YES Status (On/Off) NOTE: Door must be closed.
Attributes: Exhaust & Inlet Thermistor Reading.
When you turn on heat, the motor is turned on as well. If temp is
too high, system will automatically turn off heat.
• If the motor does not turn on, go to TEST #3, page 12.
• If no heat is detected, go to TEST #4, page 13.
Heater 1 & 2 (Electric Only) YES Status (On/Off) NOTE: Door must be closed.
Attributes: Exhaust & Inlet Thermistor Reading.
When you turn on heat, the motor is turned on as well. If temp is
too high, system will automatically turn off heat.
• If the motor does not turn on, go to TEST #3, page 12.
• If no heat is detected, go to TEST #4, page 13.
Inlet ThermistorN/A Status (F°, C°, and Resistance)
If inlet thermistor reading is out of range, go to TEST #4a, page 16.
Exhaust ThermistorN/A Status (F°, C°, and Resistance)
If exhaust thermistor reading is out of range, go to TEST #4a, page 16.
Moisture Sensor N/AStatus (Open/Closed)
• Place finger over both sensor strips. If sensor status does not change,
go to TEST #5, page 18.
Door Status N/AStatus (Open/Closed)
• If opening the door does not change status, go to TEST #7, page 20.
CCU Line Voltage 1N/A Status (L1 Voltage Measurement) NOTE: Door must be closed.
When measuring L1, the motor and heater are activated.
• If L1 is absent, go to TEST #1, page 9.
CCU Line Voltage 2 (Electric Only)N/A Status (L2 Voltage Measurement) NOTE: Door must be closed.
When measuring L2, the motor and heater are activated.
• If L2 is absent, go to TEST #1, page 9.
Air Flow N/AStatus (Normal/Restricted) NOTE: Door must be closed.
• If air flow does not turn on, go to TEST #4, page 13.
Drum Light YES Status (On/Off)
• If drum light does not turn on, go to TEST #1, page 9.
Buzzer YES Status (On/Off)
• If buzzer does not sound, go to TEST #6, page 19.
Myst Valve YES Status (On/Off) After being turned on, the myst valve automatically
deactivates after 30 seconds if not turned off.
• If myst valve does not turn on, go to TEST #9, page 21.
COMPONENT ACTIVATION CHART