How to troubleshoot samosPLAN 6 connection issues with Wieland samos PRO?
- BBenjamin RobinsonAug 14, 2025
If samosPLAN 6 cannot connect to the samosPRO Wieland gateway, ensure the SP-COP2-ENI module has power. Check the Ethernet wiring and network settings of your PC, correcting them if needed. Set your PC to a network address of 192.168.1.0. Alternatively, activate DHCP on your PC and connect the SP-COP2-ENI module and PC to a network using an active DHCP server. This addresses potential issues with preconfigured IP addresses or DHCP server allocations.