What to do if the SP-COP2-ENI module in Wieland samos PRO COMPACT Gateway does not provide any data?
- PPhillip BaxterAug 3, 2025
If the SP-COP2-ENI module in your Wieland Gateway doesn't provide data, ensure at least one Ethernet link is established. Set up the Ethernet link on your PC, verify the Ethernet wiring, and check the Ethernet settings in both the PLC and samos-PLAN5+. If Ethernet communication isn't needed, disable the Ethernet connections or PLC interfaces on the SP-COP2-ENI. Also, a duplicate IP address can cause this issue, so correct the IP address and then power cycle the system. This can happen because the module has been configured for data transmission to the PLC, but no Ethernet communication has been established or the communication is faulty or because there is a duplicate IP address detected.