Product description
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
17
Product description
910740875
samosPRO gateways allow a samosPRO system to transmit non-safety-related data for control
and diagnostic purposes to the external field bus system and to receive them.
Important safety information
ATTENTION
Do not operate a samosPRO gateway on a safety field bus!
The gateway modules are not suitable for operation with a safety field bus!
They do not only generate safety-
related field bus data (state bytes) for control and diagnostic
purposes. They do not support any safety mechanisms that would be required for communi-
cation within a safety network.
Information on the function, configuration and designations
NOTICE
Where not otherwise indicated, this manual always considers the data exchanged between
the samosPRO
system and the relevant network from the point of view of the network master
(PLC). Thus data sent to the network from the samosPRO system is termed input data, while
data received from the network is termed output data.
Configuration of samosPRO gateways takes place via the samosPLAN5+ configuration soft-
ware, using a PC or Notebook connected to the SP-COPx main module via the USB interface
or RJ45 Ethernet interface.
The safety-related logic of the samosPRO system works independently of the gateway. How-
ever, if the system has been configured in such a way that non-safety-related information from
the field bus can be integrated into the logic editor, switching off the gateway may result in
availability problems.
A samosPRO gateway can only be operated on a samosPRO system. It does not have its own
power supply. A maximum of two samosPRO gateways can be operated simultaneously for
each system.
The gateway for Modbus TCP, PROFINET IO or EtherNet/IP is integrated into the SP-COP2-ENI
controller module, while the gateways for Profibus-DP, CANopen or EtherCAT are housed in a
22.5 mm wide installation housing for 35 mm standard rails in accordance with EN 60715.
Order information:
Order data [ch. 13, p. 198]
Version, compatibility, and features
1184672907
There are various module versions and function packages for the samosPRO product family
that enable various functions. This section will give you an overview as to which module versi-
on, which function package, and/or which version of the samosPLAN5+ software you will
need to be able to use a certain function or a certain device.
Table 3: Required versions of the controller module
Available with controller module version and higher
Feature/
functionality
SP-COP1-x
SP-COP2-EN-x
SP-COP2-ENI-x
samosPLAN5+
Modbus TCP
---
---
A-01
V1.0
PROFINET IO
---
---
B-01.xx
V1.2
EtherCAT (SP-EN-ETC)
C-01.xx
C-01.xx
C-01.xx
V1.3
EtherNet/IP
---
---
D-01.xx
V1.4
PROFIBUS DP
A-01
A-01
A-01
V1.0
CANopen
A-01
A-01
A-01
V1.0
3
3.1

Table of Contents

Related product manuals