Installation and basic configuration
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
33
Electrical installation
910756235
ATTENTION
Switch off the power supply to the system!
It is possible for the system to be unexpectedly started while you are connecting the devices.
NOTICE
samosPRO gateways meet EMC conditions as set out in the EN 61000-6-2 specification
for use in an industrial environment.
In order to ensure complete EMC safety, the standard rail must be connected to functio-
nal earth (FE).
The switch box or installation housing for the samosPRO system must meet at least the
requirements of protection class IP 54.
Installation according to EN 50274.
Electrical installation as per EN 60204-1.
The external power supply of the devices must be able to bridge a short-term power ou-
tage of 20 ms in accordance with EN 60204-1.
The power supply must meet the regulations for low-voltage with safe disconnection
(SELV, PELV) in accordance with EN 60664 and EN 50178 (equipping high-voltage sys-
tems with electronic equipment).
Ensure that all modules of the samosPRO system, the connected protective devices and
the power supplies are connected to the same ground connection. The ground of the
RS-232 interface is internally connected to the ground of the power supply for the con-
troller module (A2).
Connect the shielding of all field bus and Ethernet cables to functional earth (FE) just be-
fore they lead into the switch box.