14208834.01 07/2017 EN/DE/FR/ES
16 WIKA operating instructions pressure switch, model PSD-4
EN
Menu
item
Description Parameter Factory setting
AVG1/AVG2 Damping (switching output 1 / 2) 0.00 ... 65.00 s 0.00 s
AVG3 Damping (analogue signal) 0.00 ... 65.00 s 0.00 s
UNIT Unit switching BAR, mBAR, MPA, KPA, PSI, KGcm (kg/cm²),
%
Order-related
0SET Adjust zero point / Perform Autozero”
(max. 3 % of span)
Yes / No
DISM Display value in display mode ACT = current system pressure
LOW, HIGH = Min/Max system pressure
OFF = display o
SP1/FH1 = set switching value
RP1/FL1 = set switching value
SP2/FH2 = set switching value
RP2/FL2 = set switching value
ACT
DISU Refresh rate (digital indicator) 1, 2, 5, 10 updates/second 5
DISR Rotate the indication by 180° (digital
indicator)
Yes / No
DRES Resolution (digital indicator) OPT = optimised (stable measurement value
on display with rounding factors for the last
digit, optimised to the measuring range)
FULL = maximum (nest resolution, if required
for a stable measurement value on display, a
damping must be set for the digital indicator)
OPT
RHL Clear memory (Min/Max system pressure) Yes / No
PAS Password entry 0000 = no password
Password input digit by digit
0000
TAG Measuring instrument name (TAG) 32 selectable characters (A-Z ‚0 ... 9; -
‚SPACE)
(2 spaces in sequence terminate the input and
lead to the deletion of this and the underlying
characters)
without
5. Commissioning, operation