REGULATORY INFORMATION AND INSTALLATION REQUIREMENTS
THE FOLLOWING MUST BE NOTED PRIOR TO THE INSTALLATION OF THIS APPLIANCE.
This gas appliance MUST be installed by a GAS SAFE registered installer by law. It must be installed in
accordance to these installaon instrucons and the GAS SAFETY (Installaon & Use) REGULATIONS 1998 as
amended. Non compliance of this law may lead to prosecuon and it is in the interest of you and your
family that this condion is observed.
The installaon of this appliance must be in accordance with the relevant parts of the LOCAL AND
NATIONAL BUILDING REGULATIONS as issued by the Department of the Environment or BUILDING
STANDARD (Scotland Consolidaon) REGULATIONS issued by the Scosh Development Department and
the following relevant Brish Standards:
BS5871 Part 2 Installaon of Inset Live Fuel Eect Gas Fires
BS5440 Parts 1 & 2 Installaon of Flues and Venlaon
BS6891 Installaon of Gas Pipe-work
BS6461 Part 1 Installaon of Chimneys and Flues
BS1251 Open Fireplace Components
BS715/BS EN 1856-2 Metal Flue Pipes for Gas Appliances
BS EN 1858 Chimneys Components & Concrete Flue Blocks
IS813:1996 Domesc Gas Installaon (Republic of Ireland)
Prior to installaon ensure that the gas supply is compable with the appliance, this appliance must only be
used on natural gas at a supply pressure of 20 mbar as marked on the data plate on the appliance and the
carton.
This appliance is only to be installed into a builder opening which must be constructed of non-combusble
materials conrming to BS1251 or a suitable ue-box complying with the requirements of BS715/BS EN
1856-2.
If the product is being installed into a builders opening the chimney must be at least 3 metres in height and
should be swept before installaon if it has been used for the burning of solid fuel (e.g. coal or wood). The
chimney must only serve as a ue-way to this appliance and must have no openings to any other room. The
opening should be inspected and any exposed brickwork should be repaired where necessary. The chair-
brick (if applicable) should be removed unless the minimum depth of the replace exceeds 175mm. If the
depth is less than 175mm then the chair brick MUST be removed.
If the product is being installed into a fabricated Flue-box it must be installed onto a non-combusble
surface with a thickness of at least 12mm.
This replace is also suitable for installaon into precast ue replaces which comply to the requirements
of BS EN1858. It is important to note that pre-cast ue systems should be constructed with an air gap or
some form of insulaon material between the ue block and the plastered face; pre-cast ue systems with
a plastered face directly in contact with the ue block are not correctly installed and installaon of this
appliance into such a ue system may result in the plaster cracking above the appliance. Flue-way must be
through a Class I (7” or 175mm diameter) or Class II (5” or 125mm diameter) ue of at least three meters in
height.
The ue should be checked for draw using a smoke bomb or similar, if there is a denite draw then the
installaon of the appliance can proceed.