Installation and electrical connection en
Installation and operating instructions Wilo Motor FKT 50.1, 57, 63.1, 63.2 + EMU FA 21
6.4.3.2 Check the coolant
Motor FKT 50.1, 57, 63.1
+
-
FKT 63.1
180°
Fig.8: Cooling system: Checking the coolant
FKT 50.1, 57, 63.1
+ Add/bleed the coolant
- Drain the coolant
Pump is not installed.
Pump is not connected to the mains.
Protective equipment has been put on!
1. Place the pump upright on a firm surface.WARNING!Risk of hands being crushed.
Ensure that the pump cannot fall over or slip away!
2. Place a suitable tank to collect the operating fluid.
3. Unscrew the screw plug (+).
4. Unscrew screw plug (-) and drain the operating fluid. If a shut-off ball cock is in-
stalled at the outlet opening, open the shut-off ball cock to drain.
5. Check the operating fluid:
If the operating fluid is clear, reuse operating fluid.
If the operating fluid is contaminated (cloudy/dark), add new operating fluid.
Dispose of operating fluid in accordance with the local regulations!
Notify customer service if the operating fluid contains swarf!
6. If a shut-off ball cock is installed on the outlet opening, close the shut-off ball
cock.
7. Clean the screw plug (-), replace the seal ring and screw it back in. Max. tightening
torque: 8Nm (5.9ft·lb)!
8. Pour the new operating fluid in through the hole for the screw plug (+).
Comply with the specifications for operating fluid type and quantity! When re-
cycling the operating fluid, check the quantity and if required adjust it!
9. Clean the screw plug (+), replace the seal ring and screw it back in. Max. tightening
torque: 8Nm (5.9ft·lb)!
Motor FKT 63.2
+
-
Fig.9: Cooling system: Check the coolant FKT
63.2
+ Add/bleed the coolant
- Drain the coolant
Pump is not installed.
Pump is not connected to the mains.
Protective equipment has been put on!
1. Place the pump upright on a firm surface.WARNING!Risk of hands being crushed.
Ensure that the pump cannot fall over or slip away!
2. Place a suitable tank to collect the operating fluid.
3. Unscrew the screw plug (+).
4. Unscrew screw plug (-) and drain the operating fluid. If a shut-off ball cock is in-
stalled at the outlet opening, open the shut-off ball cock to drain.
5. Check the operating fluid:
If the operating fluid is clear, reuse operating fluid.
If the operating fluid is contaminated (cloudy/dark), add new operating fluid.
Dispose of operating fluid in accordance with the local regulations!
Notify customer service if the operating fluid contains swarf!
6. If a shut-off ball cock is installed on the outlet opening, close the shut-off ball
cock.
7. Clean the screw plug (-), replace the seal ring and screw it back in. Max. tightening
torque: 8Nm (5.9ft·lb)!
8. Pour the new operating fluid in through the hole for the screw plug (+).
Comply with the specifications for operating fluid type and quantity! When re-
cycling the operating fluid, check the quantity and if required adjust it!