38 Wilo SE 06/2020
en
Install shut-off devices upstream and downstream of
the pump to facilitate pump replacement.
Align the upper shut-off device laterally.
When installing in the feed of open systems, the
safety supply must branch off upstream of the
pump (EN 12828).
Complete all welding and brazing work.
Flush the pipe system.
Do not use the pump to flush the pipe system.
Installing the pump Observe the following points when installing the pump:
Note the direction arrow on the pump housing (1).
Install glandless motor (2) horizontally, without
mechanical tension.
Place gaskets in the screwed connections.
Screw on threaded pipe unions.
Use an open-end wrench to secure the pump against
twisting and screw tightly to piping.
Re-mount the thermal insulation shell if required.
CAUTION!
An incorrect installation position may damage the pump.
Select the installation point in line with the permis
-
sible installation position (Fig. 2).
The motor must always be installed horizontally.
The electrical connection must never face upwards.
CAUTION!
Leaking water may damage the control module.
Align the upper shut-off device so that leaking
water cannot drip onto the control module (5).
If the control module is sprayed with liquid, the sur
-
face must be dried off.
1
3
2