Faults, causes and remedies en
Installation and operating instructions Wilo Motor T 12 ... 72 + EMU FA, Rexa SUPRA, Rexa SOLID 55
See “Fault: Mechanical seal leakage, sealing chamber control reports a fault
and switches the pump off”.
Fault: Pump starts up, motor protection trips after short period
1. Motor protection switch set incorrectly.
Have the adjustment of the trigger checked and corrected by a qualified elec-
trician.
2. Increased power consumption due to major voltage drop.
Have the voltage of individual phases checked by a qualified electrician. Con-
tact the electricity distribution network.
3. There are only two phases at the connection.
Have the connection checked and corrected by a qualified electrician.
4. Excessive differences in voltage between the phases.
Have the voltage of individual phases checked by a qualified electrician. Con-
tact the electricity distribution network.
5. Incorrect direction of rotation.
Have the connection corrected by a qualified electrician.
6. Increased power consumption through jammed hydraulics.
Clean the hydraulics and check the inlet.
7. The density of the fluid is too high.
Contact customer service.
Fault: Pump runs, there is no volume flow
1. There is no fluid.
Check the inlet, open all gate valves.
2. Inlet clogged.
Check the inlet and remove clogging.
3. Hydraulics jammed.
Clean the hydraulics.
4. Pipe system on the pressure side or pressure hose clogged.
Remove clogging and replace the damaged components if necessary.
5. Intermittent operation.
Check the switching system.
Fault: Pump starts, duty point is not reached
1. Inlet clogged.
Check the inlet and remove clogging.
2. Slide valves on the pressure side closed.
Open all gate valves completely.
3. Hydraulics jammed.
Clean the hydraulics.
4. Incorrect direction of rotation.
Have the connection corrected by a qualified electrician.
5. Air cushion in the pipe system.
Vent the pipe system.
If air cushions occur frequently: Locate and prevent the air intake, if required
install ventilation systems at specified locations.
6. Pump pumping against excessive pressure.
Open all gate valves on the pressure side completely.
Check the impeller shape, use other impeller shapes if required. Contact cus-
tomer service.
7. Signs of wear on the hydraulics.