36 WILO SE 05/2011
6.2 Terminal boxes
There are nine terminal boxes (Fig. 4) covering all the pump types. Table 1 lists
the assignment of terminal boxes to pump types:
Table 1: Assignment of terminal box types to pump types (see also Fig.4)
The fittings for the terminal boxes can be found in Table 2:
Table 2: Fitting of terminal boxes
1) The light indicator signals are carried by a common fibre optic cable to the cover, so that the signals are visible
from outside.
2) When mains voltage is present, the lamp lights up green
The direction of rotation indicator light lights up green when mains voltage is
present and the direction of rotation is correct; if the direction of rotation is
incorrect, the indicator light goes out (see chapter “Commissioning”).
The fault indicator light lights up red if the integral motor protection has tripped
.
Mains
connection
Max. power consumption P
1
Terminal box type
(see name plate data) TOP-RL
TOP-I
TOP-S
TOP-SD
TOP-Z TOP-D
1~ P
1
max  85 W - - - 8
95 W  P
1
max  265 W 1 1/2 1 9
320 W  P
1
max  400 W - 3/4/5 3 9
650 W  P
1
max  960 W- 5 - -
3~ P
1
max  90 W - - - 8
100 W  P
1
max  270 W 6 6 6 9
305 W  P
1
max  3125 W - 7 7 9
Terminal box
type
Direction of
rotation
indicator light
Fault signal
light
Variable speed control
(Fig. 4, item 1) (Fig. 4, item 2) (Fig. 4, item 3)
1 - - Speed selection switch, 3-step
2 - - Internal or external,
jumpering the contacts “
x1-x2” or
“x1-x3” or “x1-x4”
3 - - Speed selection switch, 3-step
4 - - Internal or external,
jumpering the contacts “
x1-x2” or
“x1-x3” or “x1-x4”
5-
2)
X
1)
Change-over switch, 2-step
6 X (internal) - Change-over switch, 3-step
7X
1)
X
1)
Change-over switch, 3-step
8X (internal)--
9X (internal)--