NOTE: This pump is equipped with a frequency
converter and may not be protected by a resid-
ual-current-operated protection switch.
Frequency converters can impair the function of
residual-current-operated protection circuits.
Exception: Residual-current-operated protection
switches which have a selective universal-cur-
rent-sensitive design are allowed.
• Labelling: RCD
• Trigger current: > 30 mA.
• Use power cables conforming to standards.
• Mains side fuse protection: max. permissible 25 A
• Trigger characteristic of the fuses: B
• You can change the orientation of the motor-
converter by quarter turn when removing the
fixing bolts of the motor and reorientating the
motor to the position wished. Re-screw bolts.
• As soon as the power supply of the converter has
been activated, a 2 second display test is carried
out, where all characters on the display are
shown.