STOVE PIPE INSTALL/ HELPFUL HINTS
Have your WiseWay stove and chimney system installed by a certified stove installer or
licensed contractor.
All installations must meet local codes.
Use 4 inch type L certified pellet exhaust venting system and the installation must meet
local codes.
This is a wood stove that burns wood pellet fuel, this means natural draft is running the
stove, it must be treated as a wood stove with the pipe installation being as vertical as
possible to obtain maximum upward draft.
Horizontal runs and elbows are discouraged.
Do not install a flue damper in the exhaust vent.
DO NOT CONNECT THIS UNIT TO CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
Chimney connector must be in good condition and kept clean. Exhaust venting system
termination requirements, including location restrictions: relationships to air inlets, distance
from windows, doors, air inlets, and distance to combustible materials MUST BE MAINTAINED
AT ALL TIMES.
For mobile home use (U.S.A. ONLY) Install with 4 inch type L pellet vent with ceiling trim plate,
attic insulation shield, flashing, storm collar and cap. Appliance must be bolted down, grounded
with 10 gauge copper wire and an outside air source must be supplied.
WARNING: DO NOT INSTALL IN A SLEEPING ROOM!
CAUTIONS: STRUCTURAL INTEGRITY OF THE HOME FLOOR, WALL, AND CEILING/ROOF MUST
BE MAINTAINED.
When this room heater is not properly installed, a house fire may result. To reduce the risk of
fire, follow the installation instructions. Contact local building or fire officials about restrictions
and installation inspection requirements in your area.
DO NOT CONNECT TO OR USE IN CONJUNCTION WITH ANY AIR DISTRIBUTION
DUCTWORK UNLESS SPECIFICALLY APPROVED FOR SUCH INSTALLATION.