27
3062049_201610
KG Top
Scrubber - Check all pipes and the pump for leaks.
- Checkthatthenozzleassemblyandthenozzlesaresecure.
- Ensure that the siphon drain is unobstructed.
- Fill the siphon with water.
- Fill the scrubber tray until water drains off through the siphon.
- Brieystartthemotortocheckthescrubberpumpdirectionofrotation;ifrequired
correct the direction of rotation.
Check the power consumption of the pump motor.
Neverpermitthescrubberpumptorundry.
Thepumpcansufferirreparabledamageifitrunsdry.
- Switch on the air intake fan
- Switch on the scrubber pump
- Adjusttheoat:Traywaterlevelatleast10mmabovethepumpintake,max.10mm
belowtheoverowoutlet
- If installed: adjust dry run protection and automatic T.D.S. (in accordance with separate
instructions supplied)
Note: On account of their production-related surface structure, mist eliminators are
subject to disruptive discharges for a limited time.
This is not an engineering defect.
Note
Commissioning
Beforellingtherefrigerantsystemwithrefrigerant,takesuitablemeasurestoensure
that no traces of residual moisture remain in the pipework (e.g. evacuate or purge the
pipework with dry nitrogen).
Checkevaporationtemperature:min.evaporationtemperature+2°C;iftheevaporation
temperatureis<+2°Cthereisariskoficeformingonthensoftheheatexchanger
obstructingorpreventingtheairow.
The direct-expansion evaporator will be unable to achieve its rated performance unless
the refrigerant used is the same as that on which the design was based (R22 or R134a).
Never permit refrigerant to escape to the environment, as otherwise there is a risk of
environmental pollution. Use a vacuum extractor of suitable design.
Note
Cooling coil
(direct-expansion evaporator)
Contacthumidier
Tomaximisetheservicelifeofthehumidiermedium,notethefollowing:
- adequate supply of circulating water (approx. 3 x evaporated volume)
- permanent humidifying of the entire surface
- airtemperature,watertemperature<40°C
- always clean in good time
- operate only with fresh water (clear in appearance, without sediment).
Changingthehumidiermedium:
Removal and installation through the inspection door:
- remove the cover plate
- removethehumidiermedium
- install new blocks.
Takecaretoinstallthehumidiermediumrightwayroundasotherwisemistwillbe
entrainedinthe airowand thehumidier performance willfall signicantlyshort of
requirements.
Note
- Checkthecoldwatertemperature:min.coldwatertemperature+2°C;
iftheevaporationtemperatureis<+2°Cthereisariskoficeformingontheheat
exchangernswhichwouldobstructorpreventtheairow.
Antifreezeagentsarehazardoustohealth.Alwayscomplywiththesafetyinstructions
issuedbythemanufactureroftheantifreezeusedonsite.