EasyManua.ls Logo

Wolf KG - Maintenance Checklist

Wolf KG
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
3062049_201610
KG TopChecklist
Recommended checklist for hygienic operation and the maintenance of air-handling systems
GenuineWOLFsparepartscanbeorderedatshortnoticebyfaxingtherequisite
information,accompaniedbytheordernumber(seeratingplate)tothisnumber:
+49 8751/74-1574.
Activity Possiblemeasure Months
Outsideair/expelledairapertures
Chamberinternals/appliancecasing
Check for contamination, damage and
corrosion
Clean and repair 12
Airlter
Check for excessive contamination and
damage (leaks)
Changetheairltersconcernedif
the last change was not more than 6
months ago, otherwise change the
entirelterstage
3
Steamhumidier
Wash with cleaning agents
Rinseanddrythehumidierchamber,
disinfect if necessary
6
Check steam wand for deposits Clean 6
Check hygiene condition 6
Heat exchanger
Check for contamination, damage and
corrosion
Clean and repair 3
Check siphon function Repair 3
Check hygiene condition 6
Fan
Check for contamination, damage and
corrosion
Clean and repair 6
Heat recovery
Check condensate tray and mist
eliminator for contamination, corrosion
and function
Repair 3
Check siphon function Repair 3
Check hygiene condition 12
Ductwork and attenuator
Check for contamination, damage and
corrosion
Clean and repair 12
Endunits
Checkendunitswithoutsideairlterfor
contamination
Replaceairlters,cleanappliance 3
Check heat exchangers in end units
withoutairltersforcontamination
Clean (vacuum cleaner) 6
Replaceairlters 12