Final location
Always install KG air-handling units in rooms where frost cannot occur.
Iftheoccurrenceoffrostatthenallocationcannotberuledout,adoptsuitablemeasures
to prevent water-containing components from freezing. If an outside thermostat is
installed ensure it is adequately insulated to prevent the air-handling unit from shutting
down inadvertently (see frost protection measures, page 25).
KGW air conditioning units are designed to be installed outdoors.
Note
Spacerequirements
Make sure a clear space equal to at least the width of the equipment units is available
on the operator side; this is the minimum space necessary for installation, operation
and maintenance (see the table below).
Footprint of space required for installation, operation and maintenance:
Fan section 0.8 x appliance width
Cooling coil, heating coil, KVS 1 x appliance width + 250 mm
Filter section up to KG 96 1 x appliance width
from KG 130 0.5 x appliance width
Inback-to-backcongurationswithside-by-sideunits,leaveclearancesasstatedabove
on both sides for installation, operation and maintenance.
Install units that require a siphon (scrubber, humidier, cooling coil, plate-type heat
exchanger, mist eliminator) in such a way as to ensure correct installation and operation
of the siphon (make adequate provision for the foundation height).
Itisadvisabletoinstallawaterprooffoundationforunitswithhumidiersand/orcooling
coils installed above rooms containing moisture-sensitive equipment (e.g. IT rooms, etc.).