38
These setting are programmed before unit ships,
and are provided for reference only. Please do
not attempt to adjust these settings without
consulting Wood-Mizer service first.
To enter the Initial Setup mode, hold the “Select” key
and immediately hold the “v“ key to enter in “Setup
mode, then release both the “Select” and “v“ keys;
the rst parameter setting screen will appear. To
set the next parameters press the same key again.
The controller will exit from the set-up mode after
the setting of the last parameter or after 10 seconds
without any activity on the keyboard.
1. Fahrenheit mode (on/o)
Screen appearance: SETUP 1
Fahrenheit ON/OFF
If the parameter is set to ON, the temperature will
be displayed in Fahrenheit, otherwise it will be
displayed in Celsius degrees.
2. Compressor enabling temperature
(20°C to 99°C/68°F to 210°F)
Screen appearance: SETUP 2
COMPRESSOR 80° F
It is the minimum temperature required to enable
the compressor. Below this temperature the
compressor will remain turned o.
3. Compressor hysteresis (0 to 20° C/F)
Screen appearance: SETUP 3
Hy COMPRESSOR 1° F
This parameter is used to dene a range around
the WB temperature setting where the status (On
or O ) of the compressor is left unchanged. This
is useful to prevent undesired oscillations due to
the measurement precision or to small uctuations
around the threshold values (see “Relay activation
conditions”).
4. Overheating threshold (0 to 20° C/F)
Screen appearance: SETUP 4
Hy VENT 2° F
It denes a threshold above the DB temperature
setting to activate the overheating relay. The relay is
turned OFF when the DB temperature decrease to
the DB set point (see “Relay activation conditions”).
5. Humidication hysteresis (0 to 20° C/F)
Screen appearance: SETUP 5
Hy SPRAY 2° F
This parameter is used to dene a range around the
WB temperature setting where the status (On or O)
of the humidication relay is left unchanged. This
is useful to prevent undesired oscillations due to
the measurement precision or to small uctuations
around the threshold values (see “Relay activation
conditions”).
6. Temperature hysteresis (0 to 20)
Screen appearance: SETUP 6
Hy Temperature 1° F
This parameter is used to dene a range around
the DB temperature setting where the status (On
or O ) of the heating relay is left unchanged. This
is useful to prevent undesired oscillations due to
the measurement precision or to small uctuations
around the threshold values (see “Relay activation
conditions”).
11. Serial Address (0 to 128) (KD150 Only)
Screen appearance: SETUP 11
Serial Add x
It is used to assign a unique identication to the
controller when it is connected to a PC. Each kiln of
the plant must have a dierent address. The address
numbers assigned should be consecutive starting
from 1.
Controller Factory Setting
Wood-Mizer
KD150 12/22/17