What to do if my Woodward 3161 Governor Controller prime mover will not accept full load?
- CCarrie BrownAug 13, 2025
First, determine if the governor is at full fuel. If YES: ensure the linkage is adjusted properly, the load isn't excessive, the voltage regulator (if used) is set properly, and the fuel stop on the prime mover is set correctly. If NO: ensure the load limit is out of the way and adjusted properly, the fuel limiter (if equipped) isn't set too low, there's adequate air pressure for the fuel limiter, the linkage isn't sticky or improperly adjusted, and if it's an electric start fuel limiter, ensure there's adequate voltage for the solenoid.