EasyManuals Logo

Xantrex Trace C35 User Manual

Xantrex Trace C35
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
©2000 Xantrex Technology Inc.
3.0 INSTALLATION
Diversion Control Mode Cabling
When using the C-Series unit as a diversion or DC load controller, the DC
load needs to be connected to the controller terminals marked as PV POS/LOAD
and COMMON NEGATIVE. The common negatives can be reversed or wired
with an appropriately sized single conductor to a more convenient location
such as a DC load center negative bus.
· Connect your DC current source (PV, wind, hydro, etc.) directly to
abattery.
· Connect an appropriately-sized cable from the positive battery terminal to
the controller terminal marked BAT POS.
· Connect a cable from the negative battery terminal to the terminal marked
COMMON NEGATIVES on the controllers circuit board.
· Connect a cable from the controllers terminal marked PV POS/LOAD to the
positive terminal of your DC diversion load.
· Connect a cable from the controllers terminal marked COMMON NEGA-
TIVES to the negative terminal of your DC diversion load.
· Tighten the terminal lugs to 20 inch-pounds for #14-10 AWG (25 for
#8 AWG, 35 for #6 AWG). Allow a little slack on the cables within the
controller and secure the wiring with strain reliefs.
NOTE: Do not use light bulbs for diversion loads. Use only resistive loads such
as air- or water-cooled heating elements.
Battery Positive + Battery Negative Diversion Load
Positive +
Diversion Load
Negative 
Figure 7
PV Load Diversion Wiring
18

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xantrex Trace C35 and is the answer not in the manual?

Xantrex Trace C35 Specifications

General IconGeneral
BrandXantrex
ModelTrace C35
CategoryController
LanguageEnglish

Related product manuals