XCHARGE C6EU DC charging station
Preventive maintenance instructions
XCHARGE Europe GmbH, Borsteler Bogen 27 A, 22453 Hamburg, Germany http://www.xcharge.com/en/
Checking the triggering be-
haviour of the RCD
3 years
10 min.
Measurement of the tripping current and tripping times with
a suitable measuring device
Inspection of the ground
fault loop impedance
3 years
15 min.
Check if the ground fault loop impedance meets local re-
quirements. The value must be sufficiently low to trip the
safety devices in the required time.
Note:
the total 1 year maintenance inspection period last on average 60 minutes, however the actual duration may vary, but
should not exceed 120 minutes.
Replacement of components
Component
replacement cycles
CCS charging plug and charging
cable
8 years or 10 000 cycles
charging plug and charging cable
CHAdeMo
8 years or 10 000 cycles
Air filter
1 year, depending on the EVSE
environment
Fans for the whole EVSE
8 years
Fan in the power module
8 years
Auxiliary power supply
12V and 24V
8 years
contactor
8 years or 10 000 cycles
Based on the results during maintenance, the site operator and/or service partner plans preventive maintenance, prepares spare
parts stocks and catches possible failures in advance to extend the life of EVSE. All results should be written down in the table and
sent annually to eu@xcharge.com to demonstrate proper maintenance of the charging station. XCHARGE's warranty is void if the
charging station has not been properly maintained.