XCHARGE C6EU DC charging station
Preventive maintenance instructions
XCHARGE Europe GmbH, Borsteler Bogen 27 A, 22453 Hamburg, Germany http://www.xcharge.com/en/
Checking the triggering be-
haviour of the RCD
Measurement of the tripping current and tripping times with
a suitable measuring device
Inspection of the ground
fault loop impedance
Check if the ground fault loop impedance meets local re-
quirements. The value must be sufficiently low to trip the
safety devices in the required time.
Note:
the total 1 year maintenance inspection period last on average 60 minutes, however the actual duration may vary, but
should not exceed 120 minutes.
Replacement of components
Duration of work for replacement
CCS charging plug and charging
cable
charging plug and charging cable
CHAdeMo
1 year, depending on the EVSE
environment
5 minutes/filter (10 minutes max.)
Auxiliary power supply
12V and 24V
20 minutes/supply (max. 30 min.)
Fuse FU1, FU2: 15 minutes
Interim reply KA1-4: 30 minutes
AC SPD: 20 minutes
Based on the results during maintenance, the site operator and/or service partner plans preventive maintenance, prepares spare
parts stocks and catches possible failures in advance to extend the life of EVSE. All results should be written down in the table and
sent annually to eu@xcharge.com to demonstrate proper maintenance of the charging station. XCHARGE's warranty is void if the
charging station has not been properly maintained.