Xtralis VESDA LCD Programmer Product Guide Xtralis VESDA
®
42 www.xtralis.com
155. Communications - The Communications screen allows settings for:
Net Delay - This function sets the maximum time for a message to travel
around the network and return to the originating device. If the message does
not return within the prescribed time, it is presumed lost and will be resent
Pref. Port - This allows you to assign a preferred port for communication
Health Check - This function sets the frequency of health-check messages
sent around the system.
DST
156. Smoke Change - This screen sets the minimum interval over which a change in
the obscuration rate should occur before an alarm is triggered, or the event is
registered in the Event Log. You can enter the required interval.
DST
157. Miscellaneous -
Units - This gives the user an option to enter and display data in S.I.
(International System of Units), or U.S. (Us Imperial measurements)
UL Version - A against this indicates that the Devices on the system are set
to meet UL specifications.
Isolate Remind - Provides an option to enable or disable the reminder beeper
when the Isolate function is enabled
Support - Displays the contact phone number for support
Device ID - This provides an option to Name and Number, Name Only or
Number Only devices connected to VESDAnet.
Refresh Map - Refreshes the VESDAnet map when a Detector Chassis is
changed
Latch Alarms - This provides a YES/NO option to latch/unlatch all Alarms
Latch Faults - This provides a YES/NO option to latch/unlatch all Faults
ADM
ADM
ADM
DST
ADM
ADM
ADM
ADM
158. Show Wiring Order - Lists all the Xtralis VESDA devices connected to VESDAnet. USR
159. LCD Screen - Select this menu to set LCD screen options. USR
160. Screen Control -
Contrast - Permits the LCD Screen Contrast setting between 0 and 10
Backlight - Controls the backlight ON and OFF function
USR
Scrn
No.
Description
Min.
Access
Level
Parameter Default Minimum Maximum
Network delay 15 seconds 10 seconds 45 seconds
Preferred port A N/A N/A
Health check 45 seconds 40 seconds 60 seconds
Open - ended none N/A N/A
Parameter Default Minimum Maximum
Min. Interval 2 seconds 2 seconds 10 seconds