How to resolve SETPOINT 2 I < 4 mA, SETPOINT 2 I < 4 mA ERROR 26 on Xylem HVL 2.015-4.220?
- CChristopher GreenSep 5, 2025
SETPOINT 2 I < 4 mA, SETPOINT 2 I < 4 mA ERROR 26 on your Xylem Water System indicates that the current signal input of required values is active, but no signal between 4-20 mA is connected. Check the external analog signal on terminals X3/22-23 and the configuration of the required values in P800 SUBMENU REQUIRED VALUES.