Inverter SIO Driver
GP-Pro EX Device/PLC Connection Manual
10
Device Setting
To display the [Individual Device Settings] dialog box, select the external device and click [Setting] from
[Device-Specific Settings] in the [Device/PLC] window. To connect multiple External Devices, click from
[Device-Specific Settings] in the [Device/PLC] window to add another External Device.
External Device Settings
To configure communication settings, use the MENU, DATA/ENTER, Up, Down, or Shift/RESET key on the
digital operator located on the front of the inverter. Refer to your External Device manual for details.
1 Press the MENU key to select [Programming].
2 Press the DATA/ENTER key.
3 Press the Up key to display the parameter you want to set.
4 Press the DATA/ENTER key.
5 Press the Up, Down, or Shift/RESET key to display the setting value.
6 Press the DATA/ENTER key.
7 Reboot the External Device.
This completes the setting of the External Device.
Parameter No. Settings Setup Description
H5-01 01 Slave address (HEX)
H5-02 3 Communication speed selection
H5-03 1 Communication parity selection
H5-04 3 Stopping method after communication error
H5-05 1 Communication error detection selection
H5-06 5 Send wait time
H5-07 1 RTS control ON/OFF