EasyManua.ls Logo

YOKOGAWA ProSafe-RS

YOKOGAWA ProSafe-RS
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Explosion Protection Instrumentation in Zone 2/Division 2
2-14
TI 32S01J30-01E
<Hazardous area Zone 2>
<Non-hazardous area>
F030207.ai
Cabinet
L2SW
SCU
SNU
SSB401
L2SW
Cabinet
SNT401
N-IO
I/O Module
FIO
I/O Module
Fiber-optic cable
S2BN1D
S2BN1D
S2NN30D
S2EN501
SEC401
Ex “ec”/Type “n” deviceEx “ec”/Type “n” device
Transient
Protection
Transient
Protection
*1
*1
*1
24 V DC
Power
Supply
(*2)
Transient
Protection
(*2)
Transient
Protection
(*2)
(*2)
*1
N-IO
I/O Module
24 V DC
Power
Supply
24 V DC
Power
Supply
*1 *1
L2SW: Layer 2 switch
SCU: Safety Control Unit
SNU: Safety Node Unit
*1: Explosion-proof wiring that is dened in EN/IEC 60079-14 and the rules/standards of each country or region.
*2: Transient protection shall be provided that is set at a level not exceeding 119 V DC at the supply terminal of S2BN1D, S2BN4D,
and S2BN5D to the equipment.
Figure Example of Ex “ec” Configuration