333495-YTG-D-0609
10 Johnson Controls Unitary Products
BHZ, BHQ and BHX Unit Limitations
Size
(Tons)
Model Unit Voltage
Unit Limitations
Applied Voltage Outdoor DB Temp
Min Max Max (°F)
024
(2.0)
BHZ 208/230-1-60 187 252 125
BHX, BHQ 208/230-1-60 187 252 115
030
(2.5)
BHZ
BHQ
208/230-1-60 187 252 125
208/230-3-60 187 252 125
460-3-60 432 504 125
036
(3.0)
BHZ
208/230-1-60 187 252 125
208/230-3-60 187 252 125
460-3-60 432 504 125
BHX
BHQ
208/230-1-60 187 252 115
208/230-3-60 187 252 115
460-3-60 432 504 115
042
(3.5)
BHZ
BHQ
208/230-1-60 187 252 125
208/230-3-60 187 252 125
460-3-60 432 504 125
048
(4.0)
BHZ
208/230-1-60 187 252 125
208/230-3-60 187 252 125
460-3-60 432 504 125
BHX
BHQ
208/230-1-60 187 252 115
208/230-3-60 187 252 115
460-3-60 432 504 115
060
(5.0)
BHZ
208/230-1-60 187 252 125
208/230-3-60 187 252 125
460-3-60 432 504 125
BHX
BHQ
208/230-1-60 187 252 115
208/230-3-60 187 252 115
460-3-60 432 504 115