Loading...
350154-YTG-C-0808
16 Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZH02411
INDOOR COIL MODEL NO. FC48D + MV12D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 700 800 900
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 23.1 25.7 25.0 28.6 30.7 24.3 26.0 26.1 28.8 31.1 25.5 26.3 27.1 28.9 31.6
S.C. 22.6 21.4 17.9 18.3 14.5 23.8 23.1 19.5 19.1 15.3 25.0 24.8 21.0 20.0 16.1
K.W. 1.12 1.14 1.14 1.16 1.17 1.13 1.14 1.14 1.16 1.18 1.15 1.15 1.15 1.17 1.19
75
T.C. 22.5 24.3 23.9 27.1 29.2 23.5 24.7 24.7 27.4 29.7 24.5 25.1 25.5 27.6 30.1
S.C. 21.9 20.9 17.5 17.8 14.0 23.0 22.4 18.9 18.7 14.8 24.0 23.8 20.3 19.7 15.5
K.W. 1.31 1.32 1.32 1.34 1.35 1.31 1.32 1.32 1.34 1.36 1.33 1.33 1.33 1.35 1.37
85
T.C. 21.8 22.9 22.8 25.6 27.7 22.6 23.4 23.4 26.0 28.2 23.4 23.8 23.9 26.4 28.7
S.C. 21.3 20.4 17.2 17.3 13.6 22.1 21.6 18.4 18.4 14.3 22.9 22.7 19.6 19.4 15.0
K.W. 1.49 1.50 1.50 1.52 1.53 1.49 1.50 1.50 1.52 1.54 1.51 1.51 1.51 1.54 1.55
95
T.C. 21.2 21.5 21.8 24.0 26.2 21.8 22.1 22.1 24.6 26.7 22.4 22.5 22.3 25.2 27.2
S.C. 20.6 20.0 16.8 16.8 13.1 21.3 20.9 17.9 18.0 13.7 21.9 21.7 18.9 19.1 14.4
K.W. 1.67 1.68 1.67 1.70 1.72 1.67 1.68 1.68 1.70 1.72 1.69 1.69 1.69 1.72 1.73
105
T.C. 20.1 20.3 20.4 22.6 24.5 20.6 20.9 20.7 23.0 25.0 21.2 21.4 20.9 23.5 25.5
S.C. 19.5 19.0 16.2 16.3 12.6 20.1 19.8 17.2 17.3 13.2 20.7 20.5 18.2 18.4 13.8
K.W. 1.93 1.93 1.93 1.95 1.97 1.93 1.94 1.93 1.96 1.98 1.95 1.95 1.94 1.97 1.99
115
T.C. 19.0 19.2 19.1 21.2 22.9 19.5 19.7 19.3 21.5 23.4 20.0 20.2 19.5 21.8 23.9
S.C. 18.5 18.1 15.5 15.8 12.0 19.0 18.8 16.6 16.7 12.6 19.6 19.4 17.6 17.6 13.2
K.W. 2.17 2.18 2.17 2.20 2.23 2.18 2.18 2.18 2.21 2.23 2.20 2.20 2.19 2.22 2.24
125
T.C. 17.9 18.0 17.7 19.8 21.3 18.4 18.5 17.9 20.0 21.8 18.9 19.1 18.1 20.2 22.2
S.C. 17.4 17.2 14.9 15.3 11.5 17.9 17.8 15.9 16.1 12.1 18.4 18.3 16.9 16.9 12.6
K.W. 2.42 2.42 2.42 2.45 2.48 2.43 2.43 2.42 2.45 2.48 2.45 2.45 2.44 2.47 2.50
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
AV36C 0.97 0.97 0.99
MV12B FC/MC/PC35B 0.96 0.96 1.00
MV12B FC/MC/PC35C 0.96 0.96 1.00
MV12B FC/MC/PC35B 0.98 0.98 1.01
MV12B FC/MC/PC35C 0.98 0.98 1.01
MV12D FC/MC/PC48D 1.00 1.00 1.00
MV12D UC48D 1.00 1.00 1.00
Variable Speed
Furnace
Coil T.C. S.C. KW
PV8*A12 FC/MC/PC32A 0.94 0.94 1.01
PV9*A12 FC/MC/PC32A 0.94 0.94 1.04
P(C,V)9*B12 FC/MC/PC35B 0.95 0.95 1.02
P(C,V)9*B12 FC/MC/PC35C 0.95 0.95 1.02
PV8*A12 FC/MC/PC37A 0.96 0.96 1.01
PV9*A12 FC/MC/PC37A 0.96 0.96 1.04
P(C,V)9*B12 FC/MC/PC43B 0.98 0.98 1.03
P(C,V)9*B12 HC36B 0.95 0.95 1.01
Y*(8,L)C*A12 FC/MC/PC30A 0.95 0.92 1.01
Y*(8,L)C*B12 FC/MC/PC30B 0.96 0.92 1.00
Y*9C*B12 FC/MC/PC30B 0.95 0.92 1.01
Y*(8,L)C*A12 FC/MC/PC32A 0.95 0.92 1.02
Y*(8,L)C*B12 FC/MC/PC35B 0.95 0.91 1.00
Y*9C*B12 FC/MC/PC35B 0.96 0.94 1.02
Y*(8,L)C*A12 FC/MC/PC36A 0.95 0.93 1.01
Y*(8,L)C*B12 FC/MC/PC36B 0.95 0.92 0.99
Y*9C*B12 FC/MC/PC36B 0.96 0.94 1.01
Y*(8,L)C*A12 FC/MC/PC37A 0.97 0.95 1.02
Y*(8,L)C*B12 FC/MC/PC43B 0.97 0.93 1.00
Y*9C*B12 FC/MC/PC43B 0.97 0.95 1.01
Y*(8,L)C*A12 HC30 0.94 0.90 1.02
Y*(8,L)C*A12 HD36 0.95 0.89 1.01
Y*(8,L)C*B12 HD36 0.94 0.88 1.00
Y*9C*B12 HD36 0.95 0.89 1.00
Y*(8,L)C*A12 UC30A 0.96 0.92 1.01
Y*(8,L)C*B12 UC30B 0.96 0.93 1.00
Y*9C*B12 UC30B 0.96 0.92 1.01
Y*(8,L)C*A12 UC36A 0.92 0.89 1.00
Y*(8,L)C*B12 UC36B 0.92 0.88 0.99
Y*9C*B12 UC36B 0.92 0.89 1.00
G*9V*A12 FC/MC/PC30A 0.95 0.92 1.02
G*9V*B12 FC/MC/PC30B 0.95 0.92 1.01
G*9V*A12 FC/MC/PC32A 0.95 0.92 1.04
G*9V*B12 FC/MC/PC35B 0.96 0.94 1.02
G*9V*A12 FC/MC/PC36A 0.95 0.92 1.02
G*9V*B12 FC/MC/PC36B 0.96 0.94 1.01
G*9V*A12 FC/MC/PC37A 0.97 0.94 1.03
G*9V*B12 FC/MC/PC43B 0.97 0.95 1.01
G*9V*A12 HC30 0.95 0.91 1.02
G*9V*A12 HD36 0.94 0.88 1.02
G*9V*B12 HD36 0.95 0.89 1.00
G*9V*A12 UC30A 0.96 0.92 1.02
G*9V*B12 UC30B 0.96 0.92 1.01
G*9V*A12 UC36A 0.92 0.88 1.02
G*9V*B12 UC36B 0.92 0.89 1.00
Variable Speed
Furnace
Coil T.C. S.C. KW