Johnson Controls Unitary Products 7
697887-YTG-H-0514
AHE60D
6HK(0,1)6500206 10.0 18.3 20.0 20 20 12 12
6HK(0,1)6500506 20.0 29.2 32.5 30 35 10 8
6HK(0,1)6500806 32.0 42.2 47.5 45 50 8 8
6HK(0,1)6501006 40.0 50.8 57.5 60 60 6 6
6HK(1,2)6501306 52.0 63.8 72.5 70 80 6 4
6HK(1,2)6501506 60.0 72.5 82.5 80 90 4 4
6HK(1,2)6501806 72.0 85.5 97.5 90 100 3 3
6HK(1,2)6502006 80.0 94.2 107.5 100 110 3 2
6HK(1,2)6502506 100.0 115.8 132.5 125 150 1 1/0
1. (0,1) - maybe 0 (no circuit breaker) or 1 (with circuit breaker).
2. (1,2) maybe 1 (with circuit breaker, no breaker jumper bar) or 2 (with circuit breaker & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
4. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60 (Continued)
Air Handler Models
Heater
Models
1,2
Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity
MOP.
3
Min Wire Size (AWG)
4
208V 230V 208V 230V 208V 230V
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60
Air
Handlers
Models
Heater
Models
Total
Heater
Amps
@240V
Min. Circuit Ampacity
MOP
1
Min. Wire Size (AWG)
2
208V 230V 208V 230V 208V 230V
Circuit Circuit Circuit
1st
3
2nd 3rd
1st
3
2nd 3rd
1st
3
2nd 3rd
1st
3
2nd 3rd
1st
3
2nd 3rd
1st
3
2nd 3rd
AHE22B
AHE24B
AHE30B
6HK16501306 52.0 22.2 37.6 – 24.6 43.3 – 25 40 – 25 45 – 10 8 – 10 8 –
6HK16501506 60.0 25.1 43.3 – 27.9 50.0 – 30 45 – 30 50 – 10 8 – 10 8 –
AHE34C
AHE36C
AHE42D
6HK16501306 52.0 23.3 37.6 – 25.7 43.3 – 25 40 – 30 45 – 10 8 – 10 8 –
6HK16501506 60.0 26.2 43.3 – 29.0 50.0 – 30 45 – 30 50 – 10 8 – 10 8 –
6HK16501806 72.0 43.5 39.0 – 49.0 45.0 – 45 40 – 50 45 – 8 8–88–
6HK16502006 80.0 47.8 43.3 – 54.0 50.0 – 50 45 – 60 50 – 8 8–68–
AHE48D
6HK16501306 52.0 25.4 37.6 – 27.8 43.3 – 30 40 – 30 45 – 10 8 – 10 8 –
6HK16501506 60.0 28.3 43.3 – 31.1 50.0 – 30 45 – 35 50 – 10 8–88–
6HK16501806 72.0 45.6 39.0 – 51.1 45.0 – 50 40 – 60 45 – 8 8–68–
6HK16502006 80.0 49.9 43.3 – 56.1 50.0 – 50 45 – 60 50 – 8 8–68–
AHE60D
6HK16501306 52.0 25.4 37.6 – 27.8 43.3 – 30 40 – 30 45 – 10 8 – 10 8 –
6HK16501506 60.0 28.3 43.3 – 31.1 50.0 – 30 45 – 35 50 – 10 8–88–
6HK16501806 72.0 45.6 39.0 – 51.1 45.0 – 50 40 – 60 45 – 8 8–68–
6HK16502006 80.0 49.9 43.3 – 56.1 50.0 – 50 45 – 60 50 – 8 8–68–
6HK16502506 100.0 49.9 43.3 21.7 56.1 50.0 25.0 50 45 25 60 50 25 8 8 10 6 8 10
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. 1st Circuit includes the blower motor amps.