4 Johnson Controls Unitary Products
697887-YTG-H-0514
AHE36C
730
85/72 49.3 45.2 38.3 31.4
80/67 43 37.3 31 24.0
75/62 34.7 28.8 22.8 16.2
70/57 26.8 23.4 20.4 16.9
855
85/72 59.1 51 44.1 36.5
80/67 49.3 42.4 35.4 27.6
75/62 39.9 33.1 26.1 18.2
70/57 31.1 26.9 23.5 19.7
1000
85/72 65.2 59.5 51.2 41.3
80/67 56.4 48.3 39.9 31.3
75/62 45.8 38.1 29.7 20.8
70/57 35.7 31.2 26.9 22.6
1190
85/72 67.5 65.9 59.8 48.7
80/67 64.9 56.7 46.2 35.7
75/62 53.5 43.2 34.1 24.0
70/57 41.4 36.6 31.5 26.2
AHE42D
820
85/72 56.6 51.1 42.8 35.6
80/67 48.6 41.1 34.8 27.6
75/62 39.4 33 26 18.3
70/57 30.5 26.6 23.1 19.6
1000
85/72 65.7 61 52.7 42.9
80/67 58 49.6 41.1 32.1
75/62 46.7 38.9 30.4 21.8
70/57 36.4 31.6 27.6 23.3
1180
85/72 67.9 71.4 60.2 48.8
80/67 65.6 56.9 47.1 37.1
75/62 53.8 45.2 34.7 24.6
70/57 42.2 37.1 31.9 27.0
1385
85/72 69.4 81 68 57.2
80/67 77.1 65.4 54.1 41.6
75/62 62.1 51 39.8 28.1
70/57 48.1 42.5 36.8 30.6
AHE48D
1000
85/72 69 59.8 51.3 41.5
80/67 56.5 48.2 39.7 29.9
75/62 45.1 36.8 28.3 18.9
70/57 34.4 31 26.8 22.5
1195
85/72 79.5 69.7 59.9 48.6
80/67 65.2 55.5 45.5 34.9
75/62 52.2 42.5 32.6 21.8
70/57 40.1 36.1 31.1 26.2
1385
85/72 90 78.1 66 54.5
80/67 73.5 62.7 51.3 38.7
75/62 59.2 48.2 36.9 24.0
70/57 45.2 41 35.4 29.7
1600
85/72 102.2 90 74.3 60.4
80/67 83.6 70.6 57.2 43.1
75/62 66.1 54 41.2 27.0
70/57 50.7 46.1 39.8 33.4
AHE60D
1190
85/72 83.6 73.7 62.9 51.6
80/67 68.2 58.4 48.4 37.1
75/62 54.9 45.3 34.8 23.9
70/57 42.2 37.3 31.9 26.9
1390
85/72 95.9 84.1 71.9 58.8
80/67 79.2 67.4 54.4 41.6
75/62 62.4 51.2 39.7 26.9
70/57 48 42.5 36.8 30.6
1565
85/72 106.3 94.2 78.5 63.5
80/67 87.6 73.9 60.2 45.9
75/62 69.3 56.8 43.5 29.7
70/57 53.1 46.9 40.5 34.1
1835
85/72 122.1 107.1 90.9 72.6
80/67 100.2 85.9 69.8 51.8
75/62 79.7 65.3 49.8 32.9
70/57 60.8 54.1 46.4 38.7
1. Actual capacity varies with the outdoor AC or HP that is used with the system.
2. Airflow is calculated for each system tonnage.
COOLING CAPACITY
1
(Continued)
Models
Rated CFM
2
Entering Air
Dry/Wet Bulb (°F)
MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG)
35/107.9 40/118.9 45/130.7 50/143.3