Johnson Controls Unitary Products 11
824755-YTG-C-0912
AIR FLOW DATA (CFM)
1
High/Low Speed Cooling and Heat Pump CFM
Cool Tap
ADJ Tap
2
AHV18 AHV24 AHV30 AHV36
High Low High Low High Low High Low
A B 805 523 1035 673 1150 748 1380 897
B B 690 449 920 598 1035 673 1208 794
A A 700 455 900 585 1000 650 1200 780
B A 600 390 800 520 900 585 1050 690
A C 630 410 810 527 900 585 1080 702
C B 575 374 776 506 920 598 1035 673
B C 540 351 720 468 810 527 945 621
D B 460 299 633 414 805 523 863 564
C A 500 325 675 440 800 520 900 585
D A 400 260 550 360 700 455 750 490
C C 450 293 608 396 720 468 810 527
D C 360 234 495 324 630 410 675 441
Cool Tap
ADJ Tap
2
AHV42 AHV48 AHV60
High Low High Low High Low
A B 1610 1047 1840 1196 2070 1346
B B 1495 972 1668 1093 1811 1179
A A 1400 910 1600 1040 1800 1170
B A 1300 845 1450 950 1575 1025
A C 1260 819 1440 936 1620 1053
C B 1380 897 1495 972 1668 1081
B C 1170 761 1305 855 1418 923
D B 1265 822 1323 863 1570 1024
C A 1200 780 1300 845 1450 940
D A 1100 715 1150 750 1365 890
C C 1080 702 1170 761 1305 846
D C 990 644 1035 675 1229 801
High/Low Speed Heat CFM
Heat Tap
ADJ Tap
2
AHV18 AHV24 AHV30 AHV36
High Low High Low High Low High Low
A Any 850 650 1100 740 1100 740 1360 900
B Any 700 600 960 650 960 650 1150 770
C Any 550 550 830 600 830 600 1000 630
D Any 400 400 580 550 580 550 720 550
Heat Tap
ADJ Tap
2
AHV42 AHV48 AHV60
High Low High Low High Low
A Any 1550 950 1775 1000 2000 1150
B Any 1350 800 1600 850 1840 1050
C Any 1150 670 1360 750 1570 950
D Any 900 550 1170 600 1370 830
1. All CFMs are shown at 0.3" w.c.external static pressure. These units have variable-speed ECM motors that automatically adjust to provide constant CFM from
0.0" to 0.4" wc. external static pressure. From 0.4" to 0.8" external static pressure, CFM is reduced by 2% per 0.1" static pressure. Operation of these units on duct
systems with external static pressure greater than 0.8" is not recommended.
At some settings, airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for
the electronic air cleaner for further details.
Data is for 208V or 230V.
2. The ADJ "D" tap should not be used.

Related product manuals