EasyManua.ls Logo

York AHV18B - Cooling Capacity

York AHV18B
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Johnson Controls Unitary Products 3
824755-YTG-C-0912
COOLING CAPACITY
1
Models
Rated CFM
2
Entering Air
Dry/Wet Bulb (°F)
MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG)
35/107.9 40/118.9 45/130.7 50/143.3
AHV18B
610
85/72 37.9 33.7 28.3 23.3
80/67 31.8 27 22.5 17.6
75/62 26.4 21.5 16.7 11.6
70/57 20.7 18.4 15.8 13.5
850
85/72 49.7 43.2 36.9 28.4
80/67 42.1 35.1 28.8 22.5
75/62 33.7 28 21.4 14.7
70/57 26.5 23.8 20.3 16.9
AHV24B
585
85/72 38.7 34.4 30.1 24.7
80/67 33.6 28.9 23.9 18.9
75/62 27.2 22.7 17.8 12.8
70/57 21.2 18.6 16.2 13.7
795
85/72 50.8 45.2 38.4 32.0
80/67 43.7 36.8 31 24.0
75/62 35.7 29.5 23.1 16.1
70/57 27.9 24.5 21 17.6
985
85/72 64.9 54 45.6 37.8
80/67 52.3 44.6 36.9 28.4
75/62 42.2 35.2 26.8 19.3
70/57 33.6 29.6 25.4 21.4
AHV30B
585
85/72 38.7 34.4 30.1 24.7
80/67 33.6 28.9 23.9 18.9
75/62 27.2 22.7 17.8 12.8
70/57 21.2 18.6 16.2 13.7
795
85/72 50.8 45.2 38.4 32.0
80/67 43.7 36.8 31 24.0
75/62 35.7 29.5 23.1 16.1
70/57 27.9 24.5 21 17.6
985
85/72 64.9 54 45.6 37.8
80/67 52.3 44.6 36.9 28.4
75/62 42.2 35.2 26.8 19.3
70/57 33.6 29.6 25.4 21.4
AHV36C
730
85/72 49.3 45.2 38.3 31.4
80/67 43 37.3 31 24.0
75/62 34.7 28.8 22.8 16.2
70/57 26.8 23.4 20.4 16.9
855
85/72 59.1 51 44.1 36.5
80/67 49.3 42.4 35.4 27.6
75/62 39.9 33.1 26.1 18.2
70/57 31.1 26.9 23.5 19.7
1000
85/72 65.2 59.5 51.2 41.3
80/67 56.4 48.3 39.9 31.3
75/62 45.8 38.1 29.7 20.8
70/57 35.7 31.2 26.9 22.6
1190
85/72 67.5 65.9 59.8 48.7
80/67 64.9 56.7 46.2 35.7
75/62 53.5 43.2 34.1 24.0
70/57 41.4 36.6 31.5 26.2
For notes see Page 4.