ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY - 208/230-1-60
Air Handler Models
Heater
Models
1,2
Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity
MOP.
3
Min Wire Size (AWG)
4
208V 230V 208V 230V 208V 230V
AHV18B
6HK(0,1)6500206 10.0 14.2 15.4 15 20 12 12
6HK(0,1)6500506 20.0 25.0 27.9 30 30 10 10
6HK(0,1)6500806 32.0 38.0 42.9 40 45 8 8
6HK(0,1)6501006 40.0 46.7 52.9 50 60 8 6
AHV24B
AHV30B
6HK(0,1)6500206 10.0 14.2 15.4 15 20 12 12
6HK(0,1)6500506 20.0 25.0 27.9 30 30 10 10
6HK(0,1)6500806 32.0 38.0 42.9 40 45 8 8
6HK(0,1)6501006 40.0 46.7 52.9 50 60 8 6
6HK(1,2)6501306 52.0 59.7 67.9 60 70 6 4
6HK(1,2)6501506 60.0 68.4 77.9 70 80 4 4
AHV36C
AHV42D
6HK(0,1)6500206 10.0 15.3 16.5 20 20 12 12
6HK(0,1)6500506 20.0 26.2 29.0 30 30 10 10
6HK(0,1)6500806 32.0 39.2 44.0 40 45 8 8
6HK(0,1)6501006 40.0 47.8 54.0 50 60 8 6
6HK(1,2)6501306 52.0 60.8 69.0 70 70 6 4
6HK(1,2)6501506 60.0 69.5 79.0 70 80 4 4
6HK(1,2)6501806 72.0 82.5 94.0 90 100 3 3
6HK(1,2)6502006 80.0 91.2 104.0 100 110 3 3
AHV48D
6HK(0,1)6500206 10.0 17.5 18.6 20 20 12 12
6HK(0,1)6500506 20.0 28.3 31.1 30 35 10 8
6HK(0,1)6500806 32.0 41.3 46.1 45 50 8 8
6HK(0,1)6501006 40.0 50.0 56.1 50 60 8 6
6HK(1,2)6501306 52.0 63.0 71.1 70 80 6 4
6HK(1,2)6501506 60.0 71.6 81.1 80 90 4 4
6HK(1,2)6501806 72.0 84.6 96.1 90 100 4 3
6HK(1,2)6502006 80.0 93.3 106.1 100 110 3 2
AHV60D
6HK(0,1)6500206 10.0 17.5 18.6 20 20 12 12
6HK(0,1)6500506 20.0 28.3 31.1 30 35 10 8
6HK(0,1)6500806 32.0 41.3 46.1 45 50 8 8
6HK(0,1)6501006 40.0 50.0 56.1 50 60 8 6
6HK(1,2)6501306 52.0 63.0 71.1 70 80 6 4
6HK(1,2)6501506 60.0 71.6 81.1 80 90 4 4
6HK(1,2)6501806 72.0 84.6 96.1 90 100 4 3
6HK(1,2)6502006 80.0 93.3 106.1 100 110 3 2
6HK(1,2)6502506 100.0 115.0 131.1 125 150 2 1/0
1. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.
2. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar.
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
4. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°
C ambient, copper wire is used, consult applicable tables of the
NEC and local codes.