York AVC48CX21 - 208;230 V-1-60 Power Supply Data (Cont.)

York AVC48CX21
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Johnson Controls Unitary Products
5151060-YTG-F-1116
48D
6HK(0,1)6500206 10 19.9 20.7 25 25
6HK(0,1)6500506 20 30.8 32.7 35 35
6HK(0,1)6500806 32 44.0 47.3 45 50
6HK(0,1)6501006 40 52.4 56.6 60 60
6HK(1,2)6501306 52 65.6 71.3 70 80
6HK(1,2)6501506 60 74.0 80.5 80 90
6HK(1,2)6501806 72 87.3 95.2 90 100
6HK(1,2)6502006 80 95.7 104.4 100 110
6HK(1,2)6502506 100 117.3 128.3 125 150
60C
6HK(0,1)6500206 10 19.9 20.7 25 25
6HK(0,1)6500506 20 30.8 32.7 35 35
6HK(0,1)6500806 32 44.0 47.3 45 50
6HK(0,1)6501006 40 52.4 56.6 60 60
6HK(1,2)6501306 52 65.6 71.3 70 80
6HK(1,2)6501506 60 74.0 80.5 80 90
6HK(1,2)6501806 72 87.3 95.2 90 100
6HK(1,2)6502006 80 95.7 104.4 100 110
60D
6HK(0,1)6500206 10 19.9 20.7 25 25
6HK(0,1)6500506 20 30.8 32.7 35 35
6HK(0,1)6500806 32 44.0 47.3 45 50
6HK(0,1)6501006 40 52.4 56.6 60 60
6HK(1,2)6501306 52 65.6 71.3 70 80
6HK(1,2)6501506 60 74.0 80.5 80 90
6HK(1,2)6501806 72 87.3 95.2 90 100
6HK(1,2)6502006 80 95.7 104.4 100 110
6HK(1,2)6502506 100 117.3 128.3 125 150
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the
National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60 (Continued)
Air Handler Models
Heater Models
1,2
Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity
MOP.
3
208V 230V 208V 230V