EasyManua.ls Logo

York DBUC 072 - Supply Air Blower Perf. 3 & 4 Ton Belt-Drive 9 Supply Air Blower Perf. 5 & 6 Ton Belt-Drive 10 Electrical Data Direct-Drive; Electrical Data Belt-Drive; Superheat, 036

York DBUC 072
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OUTDOOR
TEMPERATURE,
°
F
SUPERHEAT AT SCROLL COMPRESSOR SUCTION,
°
F, AIRFLOW = 400 CFM/TON
INDOOR WB TEMPERATURE,
°
F
55 57 59 61 63 65 67 69 71 73 75
65 25.6 26.8 28 29.2 30.4 31.6 32.8 33.3 33.9 34.4 34.9
70 20.1 21.7 23.3 24.9 26.5 28.1 29.6 30.6 31.5 32.4 33.4
75 14.6 16.6 18.5 20.5 22.5 24.5 26.5 27.8 29.1 30.5 31.8
80 9.0 11.4 13.8 16.2 18.5 20.9 23.3 25.0 26.8 28.5 30.3
85 - 6.3 9.0 11.8 14.6 17.4 20.1 22.3 24.4 26.6 28.7
90 - - 6.7 9.1 11.4 13.8 16.2 18.9 21.7 24.4 27.1
95 - - - 6.3 8.3 10.3 12.3 15.6 18.9 22.2 25.6
100 - - - 5.3 6.8 8.4 10.0 13.4 16.8 20.2 23.6
105 ----5.46.57.711.214.718.221.7
110 ------5.49.012.616.219.8
115 -------6.810.514.117.8
TABLE 12
- SUPERHEAT CHARGING TABLE FOR MODEL 036
UNIT
SIZE
POWER
SUPPLY
VOLTAGE
LIMITATIONS
(SEE NOTE 1)
SCROLL
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
(SEE NOTE 2)
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
MIN. MAX. RLA LRA
036
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
18.0
11.4
6.2
5.0
105.0
90.0
45.0
36.0
1.3
1.3
0.8
0.8
5.3
5.3
3.1
3.1
29.1
20.9
11.7
10.2
45
30
15
15
45
30
15
-
048
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
24.4
14.1
7.1
5.6
140.0
105.0
55.0
44.0
1.3
1.3
0.8
0.8
8.6
5.2
2.6
2.0
40.4
24.1
12.3
9.9
60
35
15
15
60
35
15
-
060
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
28.9
16.0
8.0
6.4
165.0
125.0
67.0
50.0
1.3
1.3
0.8
0.8
8.6
6.0
3.0
2.4
46.0
27.3
13.8
11.2
70
40
20
15
70
40
20
-
072
208/230-3-60
460-3-60
575-3-60
187
414
518
253
504
630
20.3
10.2
8.2
146.0
73.0
58.4
1.3
0.8
0.8
7.3
3.7
2.8
34.0
17.3
13.9
50
25
20
50
25
-
NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110. 2. Dual element, time delay type.
TABLE 11
- ELECTRICAL DATA (BASIC UNIT)
w/Belt-Drive Blower Motor
UNIT
SIZE
POWER
SUPPLY
VOLTAGE
LIMITATIONS
(SEE NOTE 1)
SCROLL
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
(SEE NOTE 2)
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
MIN. MAX. RLA LRA
036
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
18.0
11.4
6.2
5.0
105.0
90.0
45.0
36.0
1.3
1.3
0.8
0.8
4.4
4.4
2.2
2.2
28.2
20.0
10.8
9.3
45
30
15
15
45
30
15
-
048
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
24.4
14.1
7.1
5.6
140.0
105.0
55.0
44.0
1.3
1.3
0.8
0.8
5.0
5.0
2.2
2.2
36.8
23.9
11.9
10.1
60
35
15
15
60
35
15
-
060
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
28.9
16.0
8.0
6.4
165.0
125.0
67.0
50.0
1.3
1.3
0.8
0.8
6.6
6.6
3.3
3.3
44.0
27.9
14.1
12.1
70
40
20
15
70
40
20
-
072
208/230-3-60
460-3-60
575-3-60
187
414
518
253
504
630
20.3
10.2
8.2
146.0
73.0
58.4
1.3
0.8
0.8
6.8
3.6
3.6
33.5
17.2
14.7
50
25
20
50
25
-
NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110. 2. Dual element, time delay type.
w/Direct-Drive Blower Motor
TABLE 10
- ELECTRICAL DATA (BASIC UNIT)
530.18-N8W
Unitary Products Group 11

Table of Contents

Related product manuals