036-21339-001 Rev. C (0602)
12 Unitary Products Group
Multipliers for determining the performance with other indoor sections
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RD036S06
INDOOR COIL MODEL NO. G1FA048S21,24
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1000 1200 1400
ID DB (°F) 80 80 80 80 75 80 80 80 80 75 80 80 80 80 75
ID WB (°F) 72 67 62 55 62 72 67 62 55 62 72 67 62 55 62
75
T.C. 43.5 40.9 38.6 37.4 38.6 43.0 39.7 37.2 36.6 37.2 42.5 38.5 35.7 32.9 35.7
S.C. 20.6 25.9 31.2 32.4 26.9 22.4 28.7 33.9 34.5 28.5 24.2 31.4 35.7 32.9 30.1
KW 2.83 2.81 2.79 2.79 2.79 2.75 2.74 2.71 2.71 2.71 2.68 2.66 2.62 2.61 2.62
85
T.C. 41.6 39.0 36.8 35.4 36.8 40.9 37.8 35.3 33.5 35.3 40.3 36.7 33.9 31.6 33.9
S.C. 20.1 26.9 30.2 31.2 25.8 21.8 28.9 32.9 33.2 27.5 23.6 30.9 33.9 31.6 29.1
KW 3.07 3.03 3.00 2.99 3.00 2.99 2.95 2.91 2.89 2.91 2.92 2.86 2.81 2.79 2.81
95
T.C. 39.7 37.0 34.9 33.3 34.9 38.9 35.4 33.5 32.7 33.5 38.0 34.8 32.0 30.2 32.0
S.C. 19.6 27.8 29.1 29.9 24.8 21.3 25.3 31.8 32.2 26.4 22.9 30.4 32.0 30.2 28.0
KW 3.30 3.25 3.21 3.19 3.21 3.23 2.96 3.11 3.10 3.11 3.16 3.06 3.00 2.97 3.00
105
T.C. 37.8 35.1 33.1 31.3 33.1 36.8 34.0 31.6 30.1 31.6 35.8 33.0 30.2 28.9 30.2
S.C. 19.1 28.8 28.1 28.7 23.7 20.7 29.3 30.8 30.1 25.4 22.3 29.9 30.2 28.9 27.0
KW 3.54 3.47 3.42 3.39 3.42 3.47 3.37 3.31 3.27 3.31 3.40 3.26 3.20 3.14 3.20
115
T.C. 34.3 31.9 34.9 31.9 34.9 33.7 31.0 31.2 29.3 31.2 33.2 30.1 27.4 26.6 27.4
S.C. 18.0 26.6 29.2 29.3 25.0 19.7 26.5 30.4 29.3 24.8 21.4 27.8 27.4 26.6 24.4
KW 3.74 3.64 4.27 3.64 4.27 3.66 3.53 3.79 3.46 3.79 3.57 3.42 3.31 3.28 3.31
125
T.C. 30.8 28.8 36.8 27.3 36.8 30.7 28.1 30.7 26.0 30.7 30.6 27.3 24.6 24.3 24.6
S.C. 16.9 24.2 30.9 25.4 26.4 18.8 23.8 29.8 25.7 25.1 20.6 25.7 24.6 24.3 20.5
KW 3.95 3.81 5.13 3.71 5.13 3.84 3.69 4.28 3.57 4.28 3.74 3.58 3.43 3.42 3.43
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
N1AHB12 G2FD036S17 0.95 0.95 0.98
N1AHB12 G2FD046S17 0.98 0.98 1.00
N1VSB12 G2FD036S17 0.96 0.97 0.93
N1VSB12 G2FD046S17 1.00 1.01 0.94
N1VSC16 G2FD048S21 1.03 1.03 0.93
F2RP/F2FP036 0.97 0.97 0.98
F2RP/F2FP042 0.97 0.97 1.01
F2FP045 1.03 1.03 1.00
F2FP048 1.01 1.01 1.03
G1FA036S14 0.94 0.94 0.97
G1FA036S17,21 0.93 0.92 0.97
G1FA048S17 0.98 0.98 1.00
G2FD035S14 0.93 0.92 0.97
G2FD036S17 0.95 0.95 0.98
G2FD036S21 0.97 0.97 0.99
G2FD042S21 0.98 0.97 0.99
G2FD046S17 0.98 0.98 1.00
G2FD048S21,24 1.02 1.02 1.01
G1HD036 0.95 0.96 0.98
G1HD048 1.00 1.00 1.00
G1NA036S17L 0.99 0.97 1.00
G1NA048S21D 0.99 0.97 1.00
G1NA042S24W 1.02 1.02 1.00
G1UA036S14 0.94 0.94 0.97
G1UA036S17,21 0.93 0.92 0.97
G1UA048S17 0.98 0.98 1.00
G1UA048S21,24
1.00 1.00 1.00
Variable Speed
Furnace
Coil
T.C. S.C. KW
P1XDB12V G2FD036S17 0.95 0.94 0.94
P1DUA12V G1FA036S14 0.94 0.93 0.93
P1DUA12V G1UA036S14 0.94 0.93 0.93
P1DUA12V G2FD035S14 0.93 0.91 0.92
P1DUB16V G1FA036S17 0.94 0.94 0.92
P1DUB16V G1UA036S17 0.94 0.94 0.92
P1DUB16V G2FD036S17 0.96 0.97 0.92
P1DUB16V G2FD046S17 1.00 1.00 0.94
P1XUB12V G1FA036S17 0.93 0.91 0.92
P1XUB12V G2FD036S17 0.94 0.91 0.90
P1XUB12V G2FD046S17 0.98 0.96 0.94
P1XUC16V G1FA036S21 0.94 0.95 0.92
P1XUC16V G2FD036S21 0.98 0.98 0.93