York H2RA030S06 - Refrigerant Charge and Orifice Data (Continued); 3-Phase Matched Systems

York H2RA030S06
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
036-21121-002 Rev. B (0103)
4 Unitary Products Group
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor and for 15 feet of interconnecting line
tubing.
2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaportor + adder for line set.
5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.
Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 PHASE
ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS
Outdoor Unit H1RA036 H1RA042 H1RA048 H1RA060 H1RA076 H1RA090
Unit Orifice (s)
1
67, 71, 73 75, 78, 81 81 90
Factory R-22 Charge, lbs-oz 3 - 15 5 - 4 7 - 5 9 - 7 12 - 3 15 - 3
Indoor Coil
Coil Orifice
2
System Orifice + Additional Charge, Oz
G1NA036S17J 67 61 + 2 —————
G1NA036S21C 67 61 + 2 —————
G1NA048S21D 78 78 + 0 78 + 4
G1NA048S24P 78 78 + 0 78 + 4
G1NA060S24T 87 87 + 0
G1FA/G1UA03617/21 73 61 + 0 —————
G1FA/G1UA048S17 84 78 + 5 ————
G1FA/G1UA048S21 84 63 + 13 78 + 6 81 + 13
G1FA/G1UA060S24 90 78 + 16 90 + 5
G2FD036(S,H)17 75 61 + 3 —————
G2FD036(S,H)21 75 61 + 5 —————
G2FD042(S,H)21 78 78 + 0 ————
G2FD046(S,H)17 78 78 + 5 ————
G2FD048(S,H)21/24 78 78 + 9 81 + 15
G2FD060(S,H)24 90 90 + 5
F2RC036 7561 + 0—————
F2RP042 78
78 + 0
————
702 + 0
F2FP048 84 78 + 9 81 + 15
F2FP060 90 90 + 5
K4EU090KDBC090
TXV
3
———— 0 0
Footnotes:
1. These orifices are packed in the instruction/warranty packet of each outdoor unit.
2. These orifices are factory mounted in the flow control device of each indoor coil.
3. The TXV is factory mounted in the coil or air handler.