700699-YTG-B-0812
Johnson Controls Unitary Products 21
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on next page.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGF18S41S3(E)
INDOOR COIL MODEL NO. FC/MC/PC32
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 450 600 750
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 16.2 17.9 17.6 20.0 22.3 18.0 18.8 18.6 20.9 23.6 19.8 19.8 19.6 21.9 25.0
S.C. 16.2 14.9 12.3 12.8 10.1 18.0 17.3 14.2 14.5 11.4 19.8 19.7 16.1 16.3 12.6
KW 1.00 0.98 1.00 0.99 0.98 0.99 0.99 0.99 0.98 0.97 0.99 0.99 0.99 0.97 0.96
75
T.C. 15.3 16.9 16.8 19.0 21.2 17.1 18.0 17.7 19.9 22.4 19.0 19.1 18.7 20.8 23.6
S.C. 15.3 14.3 11.9 12.2 9.8 17.1 16.7 13.7 13.9 11.0 19.0 19.1 15.6 15.7 12.2
KW 1.17 1.15 1.17 1.16 1.14 1.16 1.15 1.16 1.15 1.13 1.14 1.14 1.15 1.14 1.12
85
T.C. 14.4 16.0 15.9 17.9 20.2 16.3 17.1 16.8 18.8 21.2 18.1 18.3 17.7 19.8 22.3
S.C. 14.4 13.8 11.4 11.6 9.4 16.3 16.1 13.3 13.4 10.6 18.1 18.3 15.1 15.1 11.8
KW 1.35 1.32 1.33 1.33 1.30 1.32 1.31 1.32 1.31 1.29 1.29 1.29 1.31 1.30 1.28
95
T.C. 13.5 15.1 15.0 16.9 19.2 15.4 16.3 15.9 17.8 20.1 17.3 17.5 16.8 18.7 20.9
S.C. 13.5 13.2 11.0 11.0 9.0 15.4 15.5 12.8 12.8 10.2 17.3 17.5 14.6 14.6 11.3
KW 1.52 1.50 1.50 1.50 1.46 1.48 1.47 1.48 1.48 1.45 1.45 1.45 1.47 1.47 1.44
105
T.C. 12.9 14.1 13.9 15.8 18.0 14.6 15.3 14.7 16.6 18.7 16.2 16.4 15.5 17.4 19.4
S.C. 12.9 12.7 10.5 10.6 8.6 14.6 14.7 12.2 12.4 9.6 16.2 16.4 14.0 14.2 10.7
KW 1.80 1.79 1.81 1.80 1.74 1.77 1.75 1.78 1.77 1.74 1.73 1.72 1.75 1.74 1.73
115
T.C. 12.4 13.2 12.9 14.7 16.8 13.7 14.3 13.6 15.5 17.3 15.1 15.4 14.2 16.2 17.9
S.C. 12.4 12.3 10.1 10.2 8.2 13.7 14.0 11.7 12.0 9.1 15.1 15.4 13.3 13.8 10.1
KW 2.07 2.07 2.11 2.09 2.01 2.04 2.02 2.06 2.05 2.01 2.00 1.98 2.02 2.01 2.01
125
T.C. 11.9 12.2 11.9 13.6 15.6 12.9 13.3 12.4 14.3 16.0 13.9 14.3 12.9 15.0 16.4
S.C. 11.9 11.9 9.6 9.9 7.7 12.9 13.2 11.1 11.6 8.6 13.9 14.3 12.7 13.4 9.5
KW 2.34 2.36 2.42 2.38 2.28 2.31 2.30 2.35 2.33 2.29 2.28 2.24 2.29 2.28 2.29
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handlers Coils T.C. S.C. KW
FC/MC/PC18 0.97 0.97 1.01
FC/MC/PC32 1.00 1.00 1.00
FC/MC/PC35 1.00 1.00 1.00
FC/MC/PC37 1.01 1.01 1.01
FC/MC/PC43 1.01 1.01 1.01
HD24 1.01 1.00 1.01
HD36 0.97 0.93 1.01
UC18 0.98 0.98 1.00
AHE18B 1.01 1.02 0.91
AHE24B 1.02 1.02 0.90
AHE30B 1.02 1.02 0.90
AHE36C 1.08 1.17 0.91
AHR18B 0.99 1.02 0.99
AHV18B 0.99 1.00 0.91
AHV24B 1.00 1.01 0.91
AHV30B 1.01 1.08 0.92
AHV36C 1.02 1.07 0.89
AV*24 1.02 1.03 0.90
AV*36 1.05 1.08 0.90
MV12B FC/MC18B 1.01 0.99 0.91
MV12B FC/MC35B 1.02 1.02 0.93
MV12B FC/MC43B 1.03 1.03 0.92
MX12B FC/MC18B 1.01 1.00 0.89
MX12B FC/MC35B 1.04 1.10 0.88
MX12B FC/MC43B 1.04 1.04 0.89
Air Handlers Coils T.C. S.C. KW