700699-YTG-B-0812
Johnson Controls Unitary Products 33
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGF60S41S4(E)
INDOOR COIL MODEL NO. FC/MC62
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1600 1800 2000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 52.3 60.4 57.1 61.8 66.7 54.1 61.4 58.6 63.6 67.7 55.9 62.5 60.2 65.3 68.7
S.C. 51.1 46.8 40.1 39.0 31.5 52.9 49.5 42.1 41.0 32.6 54.7 52.1 44.2 43.0 33.7
KW 3.12 3.16 3.15 3.19 3.23 3.14 3.17 3.17 3.20 3.25 3.15 3.18 3.18 3.21 3.26
75
T.C. 50.2 57.2 54.7 59.5 64.2 51.9 58.4 56.3 61.0 65.4 53.6 59.5 57.8 62.6 66.6
S.C. 49.1 45.8 39.1 38.2 30.5 50.8 48.5 41.1 40.2 31.6 52.4 51.1 43.2 42.3 32.8
KW 3.62 3.66 3.65 3.68 3.72 3.63 3.66 3.66 3.69 3.73 3.65 3.67 3.67 3.70 3.73
85
T.C. 48.1 54.1 52.4 57.1 61.6 49.7 55.3 53.9 58.5 63.1 51.3 56.6 55.4 60.0 64.5
S.C. 47.0 44.8 38.0 37.3 29.5 48.6 47.4 40.1 39.4 30.7 50.2 50.1 42.2 41.5 31.9
KW 4.12 4.15 4.15 4.17 4.20 4.13 4.16 4.16 4.18 4.20 4.14 4.16 4.16 4.18 4.21
95
T.C. 46.0 50.9 50.1 54.7 59.1 47.5 52.3 51.6 56.0 60.7 49.0 53.6 53.0 57.3 62.4
S.C. 45.0 43.7 37.0 36.4 28.5 46.5 46.4 39.1 38.6 29.8 47.9 49.0 41.2 40.8 31.1
KW 4.61 4.65 4.65 4.66 4.68 4.62 4.65 4.65 4.67 4.68 4.63 4.65 4.65 4.67 4.68
105
T.C. 43.4 47.6 47.3 51.8 56.5 44.7 49.0 48.6 52.9 58.0 46.1 50.5 49.9 54.1 59.4
S.C. 42.4 42.5 35.8 35.3 27.4 43.8 44.8 37.9 37.5 28.7 45.1 47.2 40.0 39.6 30.0
KW 5.40 5.43 5.45 5.43 5.43 5.40 5.42 5.44 5.43 5.42 5.39 5.41 5.44 5.43 5.42
115
T.C. 40.8 44.3 44.6 48.9 54.1 42.0 45.9 45.7 50.0 55.3 43.3 47.5 46.9 51.0 56.6
S.C. 39.9 41.3 34.6 34.3 26.3 41.1 43.3 36.7 36.4 27.6 42.3 45.3 38.8 38.5 28.9
KW 6.17 6.20 6.22 6.18 6.15 6.15 6.17 6.21 6.17 6.14 6.13 6.15 6.20 6.16 6.14
125
T.C. 38.2 41.1 41.8 46.0 51.6 39.3 42.8 42.9 47.0 52.7 40.5 44.5 43.9 47.9 53.7
S.C. 37.4 40.1 33.4 33.3 25.2 38.5 41.8 35.5 35.3 26.5 39.6 43.5 37.5 37.4 27.8
KW 6.93 6.96 6.99 6.92 6.86 6.90 6.92 6.98 6.91 6.86 6.87 6.89 6.96 6.90 6.86
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handlers Coils T.C. S.C. KW
– FC/MC/PC60 0.97 0.95 0.99
– FC/MC62 1.00 1.00 1.00
– FC64 1.02 1.05 1.00
– HD60 1.01 0.99 1.01
– UC60 0.98 0.97 1.00
AHE60D – 1.01 1.03 0.97
AHR60D – 1.00 1.01 1.02
AHV60D – 0.99 0.97 0.99
AV*60 – 0.99 0.97 0.99
MV20D FC/MC60D 1.00 0.99 0.98
MV20D FC/MC62D 1.01 1.03 0.99
MV20D FC64D 1.03 1.05 0.99
MX20D FC/MC60D 0.99 0.97 0.95
MX20D FC/MC62D 1.02 1.03 0.96
MX20D FC64D 1.03 1.06 0.95
Air Handlers Coils T.C. S.C. KW