York MVC16CN21 - COOLING CAPACITY DATA (CONTINUED)

York MVC16CN21
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Johnson Controls Unitary Products
5151065-YTG-H-0118
CM42D 1400
85/72 100.6 89.8 78.2 64.7
80/67 83.5 73.7 59.8 48.0
75/62 67.8 55.8 44.7 32.5
70/57 52.3 41.5 30.7 23.7
CM48C 1600
85/72 115.2 105.0 93.9 79.0
80/67 88.3 78.2 65.5 52.6
75/62 72.7 60.8 50.1 37.6
70/57 57.7 46.9 36.6 29.7
CM48D 1600
85/72 115.2 105.0 93.9 79.0
80/67 88.3 78.2 65.5 52.6
75/62 72.7 60.8 50.1 37.6
70/57 57.7 46.9 36.6 29.7
CM49C 1500
85/72 100.9 89.3 76.9 61.9
80/67 82.7 70.7 57.6 44.1
75/62 65.7 53.9 41.0 28.0
70/57 50.2 38.5 27.7 21.2
CM49D 1600
85/72 105.5 93.5 80.5 65.0
80/67 86.9 74.2 60.4 45.6
75/62 68.6 56.0 42.5 29.4
70/57 52.5 40.2 28.3 21.6
CM50D 1600
85/72 112.6 99.2 83.5 68.6
80/67 91.9 77.3 60.5 39.7
75/62 72.1 44.3 38.5 29.3
70/57 43.2 37.1 28.2 23.2
CM60C 1800
85/72 115.1 103.0 91.7 78.6
80/67 96.8 85.9 73.7 60.5
75/62 80.7 69.4 57.5 43.5
70/57 58.7 48.9 37.7 32.7
CM60D 1800
85/72 115.1 103.0 91.7 78.6
80/67 96.8 85.9 73.7 60.5
75/62 80.7 69.4 57.5 43.5
70/57 58.7 48.9 37.7 32.7
CM61C 1600
85/72 112.6 99.2 83.5 68.6
80/67 91.9 77.3 60.5 39.7
75/62 72.1 44.3 38.5 29.3
70/57 43.2 37.1 28.2 23.2
CM61D 1800
85/72 121.2 107.6 92.9 73.3
80/67 99.3 84.6 67.9 41.1
75/62 77.4 45.0 39.9 31.1
70/57 44.1 38.7 29.9 24.9
CM64D 1800
85/72 133.6 118.5 103.2 86.6
80/67 111.4 96.2 80.3 62.8
75/62 90.7 75.1 60.0 43.5
70/57 70.6 56.9 42.5 32.8
1. See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.
2. Airflow is calculated for each system tonnage.
COOLING CAPACITY
1
(Continued)
Models
Rated CFM
2
Entering Air
Dry/Wet Bulb (°F)
MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG)
35/107.9 40/118.9 45/130.7 50/143.3