5324339-YTG-D-1117
Johnson Controls Unitary Products 15
ADDITIONAL STATIC RESISTANCE
Size (Tons) CFM Wet Indoor Coil Economizer
1
1. The pressure drop through the economizer is greater for 100% outdoor air
than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter pressure drop based on standard filter media tested at velocities not
to exceed 300 ft/min.
Filter/Frame Kit
36 (3.0)
700 0.01 0.00 0.04
800 0.02 0.01 0.06
900 0.03 0.01 0.08
1000 0.04 0.01 0.10
1100 0.05 0.01 0.13
1200 0.06 0.02 0.16
1300 0.07 0.03 0.17
1400 0.08 0.04 0.18
48 (4.0)
1100 0.02 0.02 0.04
1200 0.03 0.02 0.04
1300 0.04 0.02 0.05
1400 0.05 0.03 0.05
1500 0.06 0.04 0.06
1600 0.07 0.04 0.07
1700 0.07 0.04 0.08
1800 0.08 0.04 0.09
1900 0.09 0.05 0.10
2000 0.09 0.05 0.11
60 (5.0)
1100 0.02 0.02 0.04
1200 0.03 0.02 0.04
1300 0.04 0.02 0.05
1400 0.05 0.03 0.05
1500 0.06 0.04 0.06
1600 0.07 0.04 0.07
1700 0.07 0.04 0.08
1800 0.08 0.04 0.09
1900 0.09 0.05 0.10
2000 0.09 0.05 0.11
NOTES:
BOTTOM DUCT DIMENSIONS (Inches)
Model ABCDEF
36, 48, 60 14 13.5 5 3.5 47.5 42
REAR DUCT DIMENSIONS (Inches)
Model A B
36, 48, 60 13.6 14
'
&
$
%
$
$
6833/<
$,5'8&7
5(7851
$,5'8&7
(
)
9,(:/22.,1*83
$7%277202)81,7
+2/(
´IRUKLJKYROWDJH
+2/(´IRU
ORZYROWDJH
$
%
$
$
6833/<
$,5'8&7
5(7851
$,5'8&7
127(6HH)LJXUHWLWOHG³8QLW'LPHQVLRQV´IRUVLGHKROHVL]HVRI
HOHFWULFDOOLQHV