5167798-YTG-J-0218
Johnson Controls Unitary Products 21
115°F 125°F
1875
77 87.5 8.8 31.3 27.3 20.4 - - - 78.2 9.7 23.0 21.8 14.9 - - -
72 80.7 8.8 47.5 40.5 33.5 26.6 - - 73.2 9.8 42.9 36.0 29.1 22.2 - -
67 73.8 8.9 63.7 53.7 46.7 39.7 32.8 - 68.3 9.9 61.8 50.3 43.4 36.5 29.6 -
62 70.1 8.8 70.1 67.8 55.6 48.7 41.7 34.7 67.5 9.8 67.5 64.1 51.2 44.3 37.4 30.5
2250
77 89.7 8.7 39.6 31.2 22.7 - - - 79.7 9.6 34.1 25.5 17.0 - - -
72 82.7 8.8 54.3 45.8 37.3 28.8 - - 74.7 9.7 50.1 41.5 33.0 24.4 - -
67 75.7 8.8 68.9 60.5 52.0 43.5 35.0 - 69.6 9.8 66.1 57.5 49.0 40.4 31.9 -
62 71.9 8.8 71.9 70.4 61.9 53.4 44.9 36.4 68.9 9.7 68.9 66.6 57.8 49.2 40.7 32.1
57 72.1 8.8 72.1 70.6 62.1 53.6 45.1 36.6 67.6 9.7 67.6 65.4 56.1 47.5 39.0 30.4
2625
77 92.0 8.7 48.0 35.0 25.0 - - - 81.3 9.5 45.2 29.3 19.1 - - -
72 84.7 8.7 61.1 51.1 41.1 31.1 - - 76.2 9.6 57.2 47.0 36.8 26.6 - -
67 77.5 8.7 74.2 67.2 57.2 47.2 37.2 - 71.0 9.7 70.4 64.8 54.6 44.4 34.2 -
62 73.7 8.7 73.7 72.9 68.1 58.1 48.1 38.1 70.3 9.6 70.3 69.2 64.4 54.2 44.0 33.8
57 73.8 8.7 73.8 73.1 68.4 58.4 48.4 38.4 69.0 9.6 69.0 67.9 62.6 52.4 42.2 32.0
3000
77 94.2 8.6 56.4 38.8 27.3 - - - 82.9 9.4 56.3 33.0 21.2 - - -
72 86.8 8.6 67.9 56.4 44.9 33.4 - - 77.6 9.5 64.4 52.5 40.7 28.8 - -
67 79.4 8.6 79.4 74.0 62.5 51.0 39.5 - 72.4 9.6 72.4 72.0 60.2 48.3 36.5 -
62 75.5 8.6 75.5 75.5 74.4 62.9 51.4 39.9 71.8 9.5 71.8 71.8 71.0 59.2 47.3 35.5
57 75.6 8.6 75.6 75.6 74.6 63.1 51.6 40.1 70.4 9.5 70.4 70.4 69.1 57.2 45.4 33.5
3375
72 87.7 8.6 72.0 59.8 47.5 35.3 - - 78.2 9.5 67.8 55.4 43.0 30.7 - -
67 80.2 8.6 80.2 77.5 66.2 54.0 41.7 - 72.9 9.6 72.9 72.9 63.7 51.3 39.0 -
62 76.2 8.6 76.2 76.2 75.7 63.5 51.2 39.0 72.3 9.5 72.3 72.3 71.9 59.6 47.2 34.8
57 76.4 8.6 76.4 76.4 75.9 63.7 51.5 39.2 70.9 9.5 70.9 70.9 70.2 57.9 45.5 33.1
3750
72 88.6 8.6 76.1 63.2 50.2 37.3 - - 78.7 9.5 71.2 58.3 45.4 32.6 - -
67 81.1 8.6 81.1 81.1 69.9 57.0 44.0 - 73.5 9.6 73.5 73.5 67.2 54.4 41.5 -
62 77.0 8.6 77.0 77.0 77.0 64.1 51.1 38.1 72.8 9.5 72.8 72.8 72.8 59.9 47.1 34.2
57 77.2 8.6 77.2 77.2 77.2 64.2 51.3 38.3 71.4 9.5 71.4 71.4 71.4 58.5 45.6 32.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF090 (7.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65