5167798-YTG-J-0218
Johnson Controls Unitary Products 23
115°F 125°F
2125
77 103.0 9.4 37.0 35.2 26.4 - - - 95.1 10.1 32.7 28.3 22.9 - - -
72 92.4 9.1 57.6 48.8 40.0 31.2 - - 84.4 9.8 53.2 44.7 36.2 27.6 - -
67 81.7 8.9 78.2 62.4 53.6 44.8 36.0 - 73.7 9.5 73.7 58.0 49.4 40.9 32.4 -
62 78.2 8.8 78.2 78.1 62.2 53.4 44.6 35.8 73.3 9.4 73.3 73.2 56.6 48.1 39.6 31.1
2550
77 103.6 9.4 50.1 39.5 28.9 - - - 94.6 10.2 48.2 35.6 25.2 - - -
72 92.9 9.2 64.9 54.4 43.8 33.2 - - 83.9 9.8 60.7 50.2 39.8 29.3 - -
67 82.1 8.9 79.8 69.2 58.7 48.1 37.5 - 73.3 9.5 73.3 64.9 54.4 43.9 33.5 -
62 78.6 8.8 78.6 78.6 68.0 57.4 46.8 36.3 72.9 9.4 72.9 72.9 62.3 51.9 41.4 31.0
57 79.5 8.9 79.5 77.6 67.0 56.4 45.8 35.3 74.4 9.5 74.4 71.5 60.2 49.7 39.2 28.8
2975
77 104.2 9.5 63.1 43.8 31.4 - - - 94.1 10.2 63.6 43.0 27.5 - - -
72 93.4 9.2 72.3 59.9 47.5 35.2 - - 83.5 9.9 68.2 55.8 43.4 31.0 - -
67 82.6 9.0 81.4 76.0 63.7 51.3 38.9 - 72.8 9.6 72.8 71.8 59.4 47.0 34.6 -
62 79.1 8.9 79.1 79.0 73.8 61.5 49.1 36.7 72.6 9.5 72.6 72.6 68.0 55.6 43.2 30.8
57 80.0 8.9 80.0 79.0 72.7 60.4 48.0 35.6 74.1 9.5 74.1 72.6 65.7 53.3 40.9 28.5
3400
77 104.8 9.5 76.1 48.0 33.9 - - - 93.6 10.3 79.1 50.4 29.8 - - -
72 93.9 9.3 79.6 65.5 51.3 37.1 - - 83.0 10.0 75.8 61.4 47.1 32.7 - -
67 83.1 9.0 83.1 82.9 68.7 54.5 40.4 - 72.4 9.6 72.4 72.4 64.3 50.0 35.6 -
62 79.5 8.9 79.5 79.5 79.7 65.5 51.3 37.2 72.2 9.5 72.2 72.2 72.2 59.4 45.0 30.7
57 80.4 9.0 80.4 80.4 78.5 64.3 50.2 36.0 73.7 9.6 73.7 73.7 71.2 56.8 42.5 28.1
3825
72 96.1 9.3 85.7 70.3 54.9 39.5 - - 85.2 10.0 81.8 66.2 50.6 35.0 - -
67 85.0 9.1 85.0 84.9 73.5 58.2 42.8 - 74.3 9.7 74.3 74.3 69.2 53.6 38.0 -
62 81.4 8.9 81.4 81.4 81.4 66.1 50.7 35.3 74.1 9.6 74.1 74.1 74.1 59.3 43.7 28.1
57 82.3 9.0 82.3 82.3 81.3 66.0 50.6 35.2 75.7 9.6 75.7 75.7 74.4 58.8 43.2 27.6
4250
72 98.3 9.3 91.7 75.1 58.5 41.9 - - 87.4 10.0 87.4 71.0 54.2 37.3 - -
67 87.0 9.1 87.0 87.0 78.4 61.8 45.2 - 76.2 9.7 76.2 76.2 74.0 57.1 40.3 -
62 83.2 9.0 83.2 83.2 83.2 66.6 50.0 33.4 76.0 9.6 76.0 76.0 76.0 59.2 42.3 25.5
57 84.2 9.0 84.2 84.2 84.2 67.6 51.0 34.4 77.6 9.6 77.6 77.6 77.6 60.7 43.9 27.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF102 (8.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65