EasyManua.ls Logo

York Predator ZF078 - Capacity Performance - ZF120 (10 Ton) (Continued)

York Predator ZF078
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5167798-YTG-J-0218
Johnson Controls Unitary Products 25
115°F 125°F
2500
77 117.2 11.2 54.3 43.9 33.2 - - - 104.6 12.1 64.4 42.9 31.5 - - -
72 106.1 10.8 74.7 63.9 53.2 42.5 - - 94.9 11.6 74.8 64.0 53.3 42.6 - -
67 95.0 10.4 95.0 84.0 73.3 62.6 51.8 - 85.2 11.1 85.2 85.2 75.2 64.5 53.8 -
62 85.5 10.1 85.5 85.5 81.6 70.9 60.1 49.4 76.3 10.8 76.3 76.3 76.3 70.2 59.4 48.7
3000
77 120.1 11.2 64.1 47.2 34.5 - - - 106.6 12.3 71.1 45.8 31.5 - - -
72 108.7 10.9 80.7 68.1 55.4 42.7 - - 96.7 11.7 78.9 66.3 53.7 41.0 - -
67 97.4 10.5 97.4 88.9 76.3 63.6 51.0 - 86.8 11.2 86.8 86.8 75.9 63.2 50.6 -
62 87.5 10.2 87.5 87.5 87.5 74.9 62.2 49.6 77.7 10.9 77.7 77.7 77.7 72.6 60.0 47.3
57 90.8 10.3 90.8 90.8 87.8 75.2 62.5 49.8 83.7 11.0 83.7 83.7 83.7 72.1 59.4 46.8
3500
77 122.9 11.3 73.9 50.5 35.9 - - - 108.6 12.4 77.9 48.7 31.5 - - -
72 111.3 10.9 86.8 72.2 57.6 43.0 - - 98.5 11.8 83.1 68.6 54.0 39.4 - -
67 99.7 10.6 99.7 93.9 79.3 64.7 50.1 - 88.4 11.3 88.4 88.4 76.5 62.0 47.4 -
62 89.6 10.3 89.6 89.6 93.5 78.9 64.3 49.7 79.2 11.0 79.2 79.2 79.2 75.0 60.5 45.9
57 93.0 10.4 93.0 93.0 91.3 76.7 62.1 47.5 85.3 11.1 85.3 85.3 85.2 70.6 56.1 41.5
4000
77 125.8 11.4 83.7 53.8 37.2 - - - 110.6 12.5 84.6 51.6 31.5 - - -
72 113.9 11.0 92.9 76.3 59.8 43.2 - - 100.3 11.9 87.3 70.8 54.3 37.8 - -
67 102.0 10.6 102.0 98.8 82.3 65.7 49.2 - 90.0 11.4 90.0 90.0 77.2 60.7 44.2 -
62 91.7 10.4 91.7 91.7 99.5 82.9 66.4 49.8 80.6 11.1 80.6 80.6 80.6 77.4 61.0 44.5
57 95.1 10.5 95.1 95.1 94.7 78.2 61.6 45.1 86.9 11.2 86.9 86.9 85.7 69.2 52.7 36.2
4500
72 115.9 11.1 99.2 81.4 63.6 45.8 - - 102.2 12.0 93.1 75.4 57.7 40.1 - -
67 103.8 10.7 103.8 102.2 87.6 69.8 52.0 - 91.7 11.5 91.7 91.7 82.0 64.4 46.7 -
62 93.3 10.4 93.3 93.3 97.2 79.4 61.6 43.8 82.2 11.1 82.2 82.2 82.2 71.2 53.5 35.8
57 96.8 10.5 96.8 96.8 96.6 78.8 61.0 43.2 88.5 11.3 88.5 88.5 87.9 70.3 52.6 34.9
5000
72 117.9 11.1 105.5 86.5 67.4 48.4 - - 104.2 12.1 98.9 80.0 61.2 42.3 - -
67 105.6 10.7 105.6 105.6 92.8 73.8 54.7 - 93.5 11.5 93.5 93.5 86.9 68.0 49.2 -
62 95.0 10.5 95.0 95.0 95.0 75.9 56.8 37.8 83.7 11.2 83.7 83.7 83.7 64.9 46.0 27.2
57 98.5 10.6 98.5 98.5 98.5 79.4 60.4 41.3 90.2 11.3 90.2 90.2 90.2 71.4 52.5 33.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF120 (10 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65

Table of Contents