036-21578-002 Rev. B (0205)
Unitary Products Group 3
* ESP (External Static Pressure) .5" WG is at furnace outlet ahead of cooling coil.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
NOTES:
1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
4. All filters must be high velocity cleanable type.
5. Air flows above 1800 CFM require either return from two sides or one side plus bottom.
ELECTRICAL AND PERFORMANCE DATA
Model
Input/Cabinet Output Blower Size Blower Max.
Over-current
Protect
Air Temp. Rise
MBH MBH In. HP Amps °F
PS9A12N040UP11 40 38 11 x 8 1/2 7.0 20 35 - 65
PS9B12N060UP11 60 56 11 x 8 1/2 7.0 20 40 - 70
PS9B12N080UP11 80 74 11 x 8 1/2 7.0 20 45 - 75
PS9C16N080UP11 80 75 11 x 10 3/4 10.2 20 45 - 75
PS9C20N080UP11 80 75 11 x 11 1 12.7 20 40 - 70
PS9C16N100UP11 100 93 11 x 10 3/4 10.2 20 45 - 75
PS9C20N100UP11 100 93 11 x 11 1 12.7 20 40 - 70
PS9D20N120UP11 120 112 11 x 11 1 12.7 20 40 - 70
PS9D20N135UP11 135 127 11 x 11 1 12.7 20 45 - 75
Model
Max. Outlet
Air Temp.
Nominal
Airflow
Cabinet
Width
Total Unit AFUE
Min. Wire Size
(awg) @ 75 ft.
One Way
Approximate
Operating Weight
°F CFM In. Amps %
PS9A12N040UP11 165 1200 14-1/2 9 94.0 14 121
PS9B12N060UP11 170 1200 17-1/2 9 92.0 14 135
PS9B12N080UP11 175 1200 17-1/2 9 92.0 14 142
PS9C16N080UP11 175 1600 21 12 92.0 14 157
PS9C20N080UP11 170 2000 21 14 92.0 12 159
PS9C16N100UP11 175 1600 21 12 92.0 14 162
PS9C20N100UP11 170 2000 21 14 92.0 12 164
PS9D20N120UP11 170 2000 24-1/2 14 92.0 12 180
PS9D20N135UP11 175 2000 24-1/2 14 92.0 12 180
BLK
WHT
GRN
BLK (HOT)
WHT (NEUTRAL)
GRN
NOMINAL
120 VOLT
LINE WIRING CONNECTIONS
HEATING AND COOLING
THERMOSTAT CONNECTIONS
HEATING AND TWO-STAGE COOLING
THERMOSTAT CONNECTIONS
ROOM
THERMOSTAT
FURNACE
CONTROL
CONDENSING
UNIT
TO AIR CONDITIONER
CONTROLS
R
W
G
Y1
C
R
G
C
COMMON T’STAT CONNECTION
Y2
Y1
W
Y/Y2
ROOM
THERMOSTAT
FURNACE
CONTROL
CONDENSING
UNIT
TO AIR CONDITIONER
CONTROLS
R
W
G
Y
C
R
W
G
C
COMMON T’STAT CONNECTION
Y/Y2