REFERENCE
General Inspection Completed See Notes
Unit inspected for shipping, storage, or rigging damage

Unit installed with proper clearances

Unit installed within slope limitations

Refrigeration system checked for gross leaks (presence of oil)

Terminal screws and wiring connections checked for tightness

Filters installed correctly and clean

Economizer hoods installed in operating position

Condensate drain trapped properly, refer to Installation Manual

Economizer damper linkage tight

Gas Heat vent hood installed

All field wiring (power and control) complete

Air Moving Inspection Completed See Notes
Alignment of drive components

Belt tension adjusted properly

Blower pulleys tight on shaft, bearing set screws tight, wheel tight to shaft

Pressure switch or transducer tubing installed properly

Exhaust Inspection Powered

Barometric Relief
Completed See Notes
Check hub for tightness

Check fan blade for clearance

Check for proper rotation

Check for proper mounting (screen faces towards unit)

Prove operation by increasing minimum setting on economizer

Economizer Inspection Standard

BAS
Completed See Notes
CO
2
sensor installed Yes

No

Check economizer setting (Reference SSE Control Board LCD menu location)

Prove economizer open/close through SSE Board Setting

Reheat Mode Normal

or Alternate

Not Applicable
Humidity Sensor (2SH0401) _____________________________________________