York RMHC 18-30 - Indoor Unit Fixing; Drain Hose

York RMHC 18-30
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENGLISH
10
The drain hose can be connected to the left or the
right side.
Veri cation of condensate water drainage:
Fill the drain pan with water and observe evacuation.
Drain hose
For left and left rear piping (Factory standard)
Drain cap
Indoor Unit Fixing
Thread the indoor unit piping and cable through the hole.
Hang the top of the unit onto the upper ridge of them in mounting plate.
Make sure that the unit is correctly hung in place by sliding it to the left, then to the right.
Press the bottom left and bottom right hand corners of the unit against the mounting plate until the xing prongs
click into place in the retainers provided to that effect.
Drainage line
Interconnection cable
Note: The condensate evacuation line should be taped to the
refrigerant lines with vinyl tape.
a) Access plate for the
condensate drainage
pump detection
(condensate pump is
available as an
accessory).
Condensate
drainage line
Vinyl tape
a
Drain hose
Drain hose is exible and can be routed to suit vari-
ous piping arrangements. The drain line must include
elbow trap (U bend). Connect a plastic condensate
pipe with an internal diameter of 12 mm.
Note: Do not put the drain hose end into water.
Drain hose
For right connection
Drain cap