York SUNLINE 2000 D3CE - Field Wiring; Electrical Data; Cooling Only & Gas Heat Units

York SUNLINE 2000 D3CE
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UNIT
SIZE
POWER
SUPPLY
COMPRESSOR
OUTDOOR
FAN
MOTOR,
(#1 & #2)
FLA, EACH
SUPPLY AIR
BLOWER
MOTOR, (FLA)
TOTAL UNIT
AMPACITY,
(AMPS)
MAX.
FUSE
SIZE
1
MIN.
WIRE SIZE
2
,
(mm
2
/AWG)RLA LRA
3 kW
4 HP
5.6 kW
7.5 HP
3 kW
4 HP
5.6 kW
7.5 HP
#1 #2 #1 #2
180 380/400/415-3+N-50 19.2 9.6 146 73 2.4 8.6 - 47.0 - 60 10 / 8
240 380/400/415-3+N-50 19.2 19.2 146 146 2.4 - 11.7 - 59.7 70 16 / 6
NOTES: 1. Slow blow type fuse.
2. Based on 105°C insulated copper conductors in conduit.
24 VOLT
TRANSFORMER
ELECTRICAL DATA - Cooling Only Units and Units With Gas Heat
FIELD WIRING - Electric/Electric and Gas/Electric Units
GRD. LUG
LINE VOLTAGE
TERMINAL
BLOCK 2TB
IN UNIT
CONTROL BOX
L1
L2
L3
N
NEUTRAL
TERMINAL
Refer to the
ELECTRICAL DATA
tables to size the
power wiring, the fuses and
the disconnect switch.
530.26-TG3YI
Unitary Products Group 13