York SUNLINE 2000 D3CE - Electrical Data - Electric Heating; Units with Supplemental Electric Heating

York SUNLINE 2000 D3CE
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UNIT
SIZE
POWER
SUPPLY
(VOLTS)
HEATER OPTION MINIMUM
CIRCUIT
AMPACITY
(AMPS)
MAXIMUM
FUSE SIZE
1
MINIMUM
WIRE SIZE
2
(mm
2
/AWG)
MODEL
OUTPUT
kW
STAGES AMPS
180
380-3+N-50
E018
E036
E054
E072
11.3
22.6
33.8
45.1
1
2
2
2
17.1
34.3
51.4
68.6
47.0
53.6
75.0
96.5
60
60
80
100
10 / 8
16 / 6
25 / 4
35 / 2
415-3+N-50
E018
E036
E054
E072
13.5
26.9
40.4
53.8
1
2
2
2
18.7
37.4
56.2
74.9
47.0
57.5
80.9
104.0
60
60
90
110
10 / 8
16 / 6
25 / 4
35 / 2
240
380-3+N-50
E018
E036
E054
E072
11.3
22.6
33.8
45.1
1
2
2
2
17.1
34.3
51.4
68.6
59.7
59.7
78.9
100.0
70
70
80
110
16 / 6
16 / 6
25 / 4
35 / 2
415-3+N-50
E018
E036
E054
E072
13.5
26.9
40.4
53.8
1
2
2
2
18.7
37.4
56.2
74.9
59.7
61.4
84.8
108.0
70
70
90
110
16 / 6
16 / 6
25 / 4
50 / 2
NOTES: 1. Slow blow type fuse.
2. Based on 105°C copper conductors.
WEIGHTS (kg. / lbs.)
BASIC
UNIT
D*CE UNITS
180 866 / 1910
240 957 / 2110
D*CG UNITS
180 975 / 2150
240 1066 / 2350
OPTIONS / ACCESSORIES
Economizer 73 / 160
Motorized Damper 68 / 150
Electric
Heaters
18 kW 11 / 25
36 kW 14 / 30
54 kW 16 / 35
72 kW 18 / 40
Roof Curb
180 79 / 175
240 84 / 185
Barometric Damper 20 / 45
Wood
Skid*
180 91 / 200
240 100 / 220
*
Allows handling of unit using 2300mm (90")
long forks.
COMPONENT DESCRIPTION
UNIT SIZE (MBH)
180 240
SUPPLY AIR
BLOWER
CENTRIFUGAL BLOWER
DIA. x WD. (mm) 381 x 381 457 x 381
DIA. x WD. (in.) 15 x 15 18 x 15
FAN MOTOR kW / HP 3.7 / 5 5.6 / 7.5
INDOOR
COIL
ROWS DEEP 3 3
FINS PER 25mm (1 in.) 13.5 13.5
FACE AREA m
2
/ Ft.
2
1.45 / 15.5 1.92 / 20.5
OUTDOOR
FANS
(Two Per Unit)
PROPELLER DIA. mm / in. 762 / 30 (ea.)762 / 30 (ea.)
FAN MOTOR kW / HP 0.7 / 1 (ea.) 0.7 / 1 (ea.)
NOMINAL AIRFLOW
m
3
/ s 2.83 (ea.) 3.78 (ea.)
CFM 6000 (ea.) 8000 (ea.)
OUTDOOR
COIL
ROWS DEEP 2 2
FINS PER 25mm (1 in.) 13 20
FACE AREA m
2
/ Ft.
2
3.35 / 36.0 4.02 / 43.3
COMPRESSOR
(Qty. Per Unit)
TANDEM (10 TON NOMINAL CAPACITY) 1* 2
HERMETIC (5 TON NOMINAL CAPACITY) 1 -
AIR
FILTERS
QUANTITY PER UNIT
406 x 508 x 51 (mm)
-4
16 x 20 x 2 (in.)
QUANTITY PER UNIT
406 x 635 x 51 (mm)
-4
16 x 25 x 2 (in.)
QUANTITY PER UNIT
457 x 610 x 51 (mm)
5-
18 x 24 x 2 (in.)
TOTAL FACE AREA m
2
/ Ft.
2
1.40 / 15.0 1.87 / 20.0
CHARGE REFRIGERANT 22
SYS. #1 ( kg. / lbs.) 7.94 / 17.5 8.16 / 18.0
SYS. #2 (kg. / lbs.) 3.86 / 8.5 8.16 / 18.0
*
This compressor will be energized first.
PHYSICAL DATA
ELECTRICAL DATA
- Units With Supplemental Electric Heating