036-21083-007-A-0404
Unitary Products Group 5
TABLE 6: SYSTEM COOLING CAPACITIES AND POWER REQUIREMENTS
Air On Cool-
ing Coil
Temperature of Air on Condenser
95
°F 105°F115°F
Total
Cap.,
MBH
Power
Input,
KW
Sensible Capacity, MBH
Total
Cap.
MBH
Power
Input,
KW
Sensible Capacity, MBH
Total
Cap.,
MBH
Power
Input,
KW
Sensible Capacity, MBH
CFM
WB
°F
Entering Dry Bulb,
°F Entering Dry Bulb, °F Entering Dry Bulb, °F
86 80 74 68 86 80 74 68 86 80 74 68
H5CE090/K4EU090
3600
72 100 8.5 75 53 32 - 96 9.5 73 52 31 - 93 10.4 72 50 29 -
67 93 8.3 92 70 49 27 89 9.3 88 68 47 26 85 10.2
85 67 45 24
62 82 8.0
82 82 61 39 81 9.0 81 81 60 38 80 10.0 80 80 58 37
57 91 8.1
91 88 67 45 89 9.0 89 84 63 41 87 9.9 87 80 58 37
3000
7297 8.5 664931 - 939.5654830 - 8810.5644729 -
67 91 8.2 82 64 47 29 86 9.2 80 63 45 28 81 10.2 79 62 44 27
62 80 8.0
80 78 61 43 78 9.0 78 76 59 41 76 10.1 76 74 57 39
57 89 8.0
89 81 63 46 86 9.0 86 77 60 42 83 9.9 83 74 56 39
2400
7291 8.4 574330 - 889.3564228 - 8510.3544127 -
67 86 8.1 71 57 43 30 82 9.1 69 55 42 28 78 10.0 67 54 40 26
62 75 7.9 75 69 56 42 74 8.9 74 67 53 40 73 9.9
73 65 51 38
57 84 7.9
84 72 58 44 82 8.8 81 68 54 41 80 9.7 78 64 51 37
H5CE090/K3EU120
4200
72 104 8.5 84 59 34 - 97 9.5 82 57 32 - 90 10.4 80 55 30 -
67 97 8.3 97 80 55 30 92 9.2
92 77 52 27 86 10.2 86 75 50 25
62 91 8.2 91 91 65 40 84 9.1 84 84 59 34 78 10.0 78 78 53 28
57 91 8.2 91 91 66 41 86 9.1 86 86 61 36 81 10.0 81 81 56 31
3500
72 102 8.4 75 54 34 - 96 9.4 73 53 32 - 91 10.3 71 51 31 -
67 95 8.2 94 74 53 33 91 9.1 91 72 51 31 87 10.1 87 70 49 29
62 89 8.1 89 88 68 48 84 9.0
84 85 64 44 79 9.9 79 81 60 40
57 89 8.1 89 89 69 48 85 9.0
85 85 65 44 81 9.9 81 81 61 41
2800
7297 8.4 634731 - 919.3624630 - 8510.2604428 -
67 91 8.2 80 64 48 32 86 9.1 78 62 47 31 81 10.0 77 61 45 29
62 85 8.0
85 77 61 45 79 8.9 79 74 58 42 74 9.9 74 70 54 38
57 86 8.1
86 78 62 46 81 8.9 81 74 58 52 76 9.8 76 71 55 39
H3CE120/K3EU120
4400
72 137 11.1 95 69 43 - 133 12.4 94 68 42 - 129 13.6 93 67 41 -
67 126 11.1 112 93 67 40 120 12.3 109 91 64 38 114 13.4 105 88 62 36
62 113 10.7
113 111 84 58 109 12.0 109 108 82 55 106 13.2 106 106 79 53
57 113 10.7
113 113 87 60 109 12.0 109 109 83 57 106 13.2 106 106 80 53
4000
72 134 11.3 90 66 43 20 130 12.5 89 66 42 19 125 13.6 88 65 42 18
67 123 11.3 110 89 66 42 117 12.3 106 87 64 41 111 13.4 102 86 62 39
62 110 10.9
110 106 83 59 106 12.0 106 104 81 57 103 13.2 103 102 78 55
57 110 10.9
110 110 87 64 106 12.0 106 106 83 60 103 13.2 103 102 79 56
3000
72 114 11.1 70 53 35 18 112 12.3 69 52 35 18 110 13.6 69 52 35 18
67 104 11.0 88 70 53 36 101 12.2 87 70 52 35 98 13.4 86 69 52 34
62 94 10.7
94 84 67 50 92 11.9 92 83 66 49 90 13.2 90 82 64 47
57 94 10.7
94 87 70 53 92 11.9 92 85 68 50 90 13.2 90 82 65 48
H3CE120/K3EU180
4700
72 140 11.7 101 74 46 19 135 12.8 100 72 45 17 129 13.9 98 71 43 16
67 129 11.4 119 95 67 40 124 12.5 115 94 67 39 119 13.6 110 93 66 38
62 120 11.2
120 115 87 60 115 12.3 115 113 85 58 112 13.4 112 112 83 56
57 120 11.2
120 119 91 64 115 12.3 115 115 88 61 112 13.4 112 112 85 57
HCE150/K3EU180
6250
72 163 13.7 135 99 63 - 156 15.1 132 96 60 149 16.8 129 94 58 -
67 157 13.5
157 130 94 57 151 15.0 151 127 91 55 145 16.7 145 124 89 52
62 157 13.5
157 147 125 89 151 15.0 151 141 122 87 144 16.7 144 135 119 84
57 156 13.5
156 147 137 119 150 15.0 150 141 132 116 144 16.7 144 135 126 113
5000
72 160 13.6 121 90 60 - 153 15.0 118 88 57 - 145 16.7 115 85 55 -
67 150 13.3 144 117 87 56 144 14.8 141 114 84 53 138 16.5
138 111 81 51
62 149 13.3
149 139 113 83 143 14.8 143 134 110 80 137 16.5 137 129 107 77
57 148 13.3
148 139 131 108 143 14.8 143 134 125 105 137 16.5 137 129 120 102
All Sensible Capacity
Nominal Rating
Note: These capacities are gross ratings. For net capacities, determine
the KW requirement of the supply air blower motor per the published
BLOWER PERFORMANCE data. Convert KW to MBH per the following
equation and deduct this equivalent heat from the gross cooling ratings.
Blower Motor KW x
3.415 MBH
= Blower Motor (MBH)
KW
The KW input ratings listed above include the compressor and condenser fan motor(s).